6.  Over Excitation Protection

 

  This  AVR  has  over  Excitation  Protection 

preventing  the  generator  from  working  under 
unusually  high  excitation.  Excitation  Protection 
includes generator overload, accident removal of 
sensing  wires,  and  incorrect  voltage  setting. 
When  problems  occur,  the  AVR  will  gradually 
shutdown  the  excitation  voltage  to  the  minimum 
residual  voltage.  If  the  O/E  LED  turn  ON  and 
stays ON, you need to reset the AVR by shutting 
the  engine  for  10  seconds.  When  working  the 
generator in parallel this protection is not required, 
the  user  can  disable  this  function  by  switching 
DIP switch SW4 to ON position, vice versa. 

4.  NOTICE OF USE 

1.  Installation Notice

(Refer to Figure 2 and 4). 

  Only,  a  trained  professional  can  Installation, 

calibrate and inspections this AVR. 

  Install  this  AVR  inside  the  generator  enclosure 

away from moisture, corrosion and from any easy 
to reach area. 

2.  Generator Operation Notice

 

  During operation, the temperature on the surface 

of the AVR can reach higher the 60 

°

C / 140

°

F. 

  “DANGER”  When  the  AVR  is  working  never 

touch  or  ground  the  heat  sink  on  the  AVR.  The 
AVR heat sink is an electrically live terminal.   

 

A  warning  sticker  is  in  place  on  top  of  the  heat 

sink.

 

 

5.  FIELD FLASHING 

When  operating  this  AVR  for  the  first  time,  the 
polarity of the residual magnetism may be reversed 
or  too  weak  to  achieve  the  necessary  build-up  on 
the regulator. If reversing the field connections does 
not induce build-up, and the residual voltage is less 
than  5  VAC,  shut  down  the  Prime-mover  and 
proceed with the following steps

 

1.  Stop the generator and disconnect the field wires 

(F+  and  F

),  apply  a  DC  Voltage  using  a 

batteries positive terminal to F+ and the negative 
terminal to F

, using a current-limiting resistor of 

3~5 ohms 20 watt. 

2.   Allow approximately 3 seconds before removing 

the battery. 

 

 

 

3.   Disconnect  the  AVR  AC  power  input  terminals 

and  restart  the  generator,  re-measure  the 
residual  voltage.  If  this  voltage  is  greater  than 
5VAC,  reconnect  voltage  regulator,  and  voltage 
build-up  should  be  successful.  If  measured  less 
than 5VAC, repeat steps 5.1 and 5.2. 

4.   If repeating steps  5.1 and  5.2  does  not result  in 

generator  voltage  build-up,  and  residual  is 
greater  than  5VAC,  replace  with  a  new  voltage 
regulator. 

CAUTION 

Over  excite  may  damage  the  AVR  or  the 
exciter. 

 
 

Summary of Contents for EA16

Page 1: ...sal 16Amp Self Excited Automatic Voltage Regulator for use in 220 380 440 480 VAC brushless generators with paralleling compatibility Headquarters No 3 Lane 201 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw ...

Page 2: ...is an update of the EA15A AVR It is similar to the original EA15A in power and voltage sensing capabilities but with new enhanced paralleling functions the user can now select the CT inputs either 1 5 Amp or use new A1 A2 analogue signal inputs terminals for use with PLC paralleling controls It has new over voltage excitation safety circuits to prevent damage caused by the accidental detachment of...

Page 3: ... the manufacture of the Paralleling control PLC 2 DROOP Select switch K or L pending on the secondary current of the CT that you are using Voltage droop works when the CT and the AVR senses that the output of the generator voltage and current waveforms are out of synch and the AVR droops the output voltage of the generator to correct it 3 STAB If the generator output voltage oscillate adjusting th...

Page 4: ...he 60 C 140 F DANGER When the AVR is working never touch or ground the heat sink on the AVR The AVR heat sink is an electrically live terminal A warning sticker is in place on top of the heat sink 5 FIELD FLASHING When operating this AVR for the first time the polarity of the residual magnetism may be reversed or too weak to achieve the necessary build up on the regulator If reversing the field co...

Page 5: ...ection P1 VR1 EXT VR Field GEN VR2 A1 A2 VS1 F P2 F K VS2 L R T N S Field EXT VR VR1 P1 VR2 A2 A1 VS1 F P2 F L VS2 K GEN T N S R EA16A EA16A GEN EXT VR K VR1 VR2 A1 F P2 P1 VS1 F VS2 A2 L T N R S EA16A Field Figure 2 Paralleling Connection Figure 4 380 480V Connection Field EXT VR EA16 VR2 VR1 A2 A1 F VS1 P1 P2 F L VS2 K GEN T N S R Aux Winding 60 300v Figure 5 Auxiliary Winding ...

Page 6: ... procedure carefully and adjust again U F protection activated Increase generator speed Out voltage low U F activated Incorrect voltage selection Read user s manual to select correct voltage Poor adjustment is made Read start procedure carefully and adjust again Out voltage high Incorrect voltage selection Read user s manual to select correct voltage Poor adjustment is made Read start procedure ca...

Reviews: