background image

 
 

______________________________________________________________________________________ 

EA05A

 

3

 

1. Before you turn on the generator, please turn the 

voltage  adjustment  and  stability  adjustment  full 
anti-clockwise. After the generator  is on and run 
stably,  turn  the  voltage  adjustment  clockwise  to 
reach  the  required  out  voltage.  (If  there  is  an 
external 

potentiometer, 

turn 

the 

external 

potentiometer to the middle position before adjust 
internal voltage potentiometer.) 

2. Adjust  “Stability  Adjustment”  clockwise  slowly  to 

change the feedback time between AVR and the 
generator.  If  the  adjustment  is  too  big,  it  might 
cause the voltage  instable. If too small, the  load 
voltage will change too much at heavy load. Our 
suggestion is to trace by the multi-meter DCV. To 
adjust  “stability  adjustment”,  you  just  need  to 
make the multi-meter waving smaller. It can also 
improve the full load’s voltage drift rate. 

4.  FIELD FLASHING 

When the regulator is operated with the generator for 
the first  time, the  polarity  of residual magnetism may 
be  reversed  or  too  small  to  achieve  the  necessary 
build-up voltage for the regulator. If reversing the field 

connections does not induce build-up, and the residual 
voltage is less than the specified value of 5 Vac, shut 
down the Prime-mover and proceed with the following 
steps : 

1. With the Prime-mover at rest and the regulator’s 

field  output  wires  disconnected,  apply  a  DC 
source ( NOT grounded ) of not more than 3~12 
Vdc  with  Positive  to  F+  and  Negative  to  F-,  in 
series with a current-limiting resistor of 3~5 ohms 
20 watt.    (The set battery is a suitable source.) 

2. Allow  approximately  3  seconds  before  removing 

the DC source. 

3. With the voltage regulator disconnected ( wires 3 

and  4  ),  start  the  prime mover  and  measure  the 
“  residual  ”  voltage  available  at  the  auxiliary 
winding.  If  this  voltage  is  greater  than  5  Vac, 
reconnect voltage regulator, and voltage build-up 
should  be  successful.  If  less  than  5  Vac  is 
measured, repeat field flashing procedure. 

4. If  repeating  steps  a.  and  b.  does  not  result  in 

generator  voltage  build-up,  and  residual  is 
greater than 5 Vac, replace voltage regulator. 

 
 

5.  TROUBLE SHOOTING 

SYMPTOM

 

CAUSE 

CORRECTION 

Engine speed is too low.

 

Please refer to the Generator Manual. 

Residual voltage is too low. 
 

Please refer to the section introduction of 
excite. 

B,C,F+,F- wires are not connected well. 

Please refer to Figure 2 ~ Figure 5. 

Voltage does not 

build up 

Defective Generator. 

Please refer to the Generator Manual. 

The input wiring of A,B,C are not correct.  Please refer to Figure 2 ~ Figure 5. 

Check the external potentiometer. 

Check wiring and potentiometer. 

Under frequency. 

Please refer to the Generator Manual. 

The exciter does not match the AVR. 

Please refer to the Generator Manual. 

Out voltage low 

The  voltage  /  frequency  selector  setting 
is not correct. 

Please refer to Figure 7. 
 

Fuse blown 

The  exciter  flash  is  too  large  or  wiring 
doesn’t connect well. 

Please refer to the Generator Manual. 
Please refer to Figure 2 ~ Figure 5. 

A,C  terminals  are  not  connect  or  wiring 
incorrect. 

Please refer to Figure 2 ~ Figure 5. 
 

Out voltage high 

The  voltage  /  frequency  selector  setting 
is not correct. 

Please refer to Figure 7. 
 

Out voltage instable  Stability Adjustment doesn’t adjust well. 

 

Please refer to the section introduction of 
Adjustment. 

P.S. Please use the fuse of the original plant. 

All manuals and user guides at all-guides.com

Summary of Contents for EA05A

Page 1: ...1 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw Self Excited Automatic Voltage Regulator 5 Amp AVR For General Generators All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...g N phase as the detective input It will also cause the voltage imbalance EA05A can improve the above situation and increase the generator s rated voltage usage space such as 380V 440V We can all detect by the phase voltage 1 When the rated phase voltage of the generator is 220VAC the input terminals B C and sensing terminals A C can join together as show as figure3 It s the original setting or co...

Page 3: ...e source 2 Allow approximately 3 seconds before removing the DC source 3 With the voltage regulator disconnected wires 3 and 4 start the prime mover and measure the residual voltage available at the auxiliary winding If this voltage is greater than 5 Vac reconnect voltage regulator and voltage build up should be successful If less than 5 Vac is measured repeat field flashing procedure 4 If repeati...

Page 4: ...DIP 1000 OHM EXT VR Frequency Selector Volt Field G 380V 60HZ 380V 50HZ STAB U F 3 2 1 ON VOLT C 3 2 1 ON B F F A ON R T S N 3 1 2 UFRO DIP 1000 OHM EXT VR Frequency Selector Volt Field 220V 60HZ 220V 50HZ 2 1 3 ON 2 1 3 ON STAB U F VOLT B C F F A R T S N 3 ON 1 2 G UFRO DIP 1000 OHM EXT VR Frequency Selector Volt Figure 1 Figure 2 Figure 3 Figure 4 UFRO DIP All manuals and user guides at all guid...

Page 5: ... 5 Flash with Battery Figure 6 Figure 7 Figure 8 Figure 9 GENERATOR OUTPUT VOLTAGE GENERATOR OUTPUT VOLTAGE SOFT START V Sec 1 0 FREQUENCY HZ 10 20 40 30 50 60 0 2 60HZ OF MONINAL 80 20 40 60 50HZ 120 100 OF MONINAL 80 20 40 60 120 100 3 2 1 Field ON 440V 60HZ 440V 50HZ ON 1 1 STAB U F 3 2 VOLT C B 3 2 A F F ON R T S N G UFRO DIP 1000 OHM EXT VR Frequency Selector Volt All manuals and user guides ...

Reviews: