EA05A

 

1.  INTRODUCTION 

Sensing Inp

uuuu

 

 

Voltage 

220 / 380 / 440 VAC, 1 phase2 wire 

 

DIP switch selectable 

 

Frequency 

50 / 60 Hz, DIP switch selectable 

Power Input 

 

Voltage 

100 ~ 300 VAC, 1 phase 2 wire 

Output 

 

Voltage 

Max. 90 VDC @ 240 VAC input 

 

Current 

Continuous 5A 

 

Intermittent 7A for 10 sec 

 

Resistance 

Min. 15 ohm    Max. 100 ohm 

Voltage Regulation 

 

< ± 0.5% ( with 4% engine governing ) 

Voltage Build-up 

 

Residual voltage at AVR terminal > 5 VAC 

Thermal Drift 

 

0.03% per 

°

C change in AVR ambient

 

External Volts Adjustmen 

 

± 7% with 1K ohm 1 watt trimmer 

EMI Suppression 

 

Internal electromagnetic interference filtering 

Unit Power Dissipation 

 

Max. 8 watt 

Under Frequency Protection (Factory Setting) 

 

60 Hz system presets knee point at 55 Hz 

 

50 Hz system presets knee point at 45 Hz 

Soft Start Ramp Time 

 

3 sec. 

Dimensions 

 

101mm L * 69mm W * 47.5mm H 

Weight 

 

183g ± 2%

 

 

 

2.  WIRING 

When generator supply is over load, N phase will be 
different  with  the  sharing  load  by  3  phases  (load 
imbalance).  Hence,  the  voltage  from  N  phase  to  3 
phases  (R.S.T.)  will  be  altered.  When  the  rated 
voltage of the traditional single input’s AVR is above 
220V, it will increase the voltage drift rate by using N 
phase  as  the  detective  input.  It  will  also  cause  the 
voltage imbalance. 

EA05A  can  improve  the  above  situation,  and 
increase the generator’s rated voltage usage space, 
such  as  380V,  440V.  We  can  all  detect  by  the 
“phase voltage”. 

1. When the rated phase voltage of the generator is 

220VAC,  the  input  terminals  B,  C  and  sensing 
terminals  A,  C  can  join  together  (as  show  as 
figure3.  It’s  the  original  setting).or  connect 
independent.(as show as figure2). 

2. When the rated phase voltage of the generator is 

380V, 440V, the input terminals B, C and sensing 
terminals A, C must separate connect the wiring 
(as  show  as  Figure  4  or  figure  5).  The  voltage 
between B and C must not be over 300 VAC. 

 

3. F+ F- terminals connect to the generator field. (J 

and K) 

FEXT.VR is the potentiometer (1K

 1W). These two 

terminals 

must 

be 

by-pass 

when 

external 

potentiometer is needless. 

P.S.  :  A,  B,  C,  F+  F-  the  usage  of  wire  gauge  are 

AWG16 or 1.25 mm2 85

°

C above 600V. 

The  EXT.VR  connection  wires  must  be  made  of 
isolated wiring. 

3.  ADJUSTMENTS 

The  voltage  setting  for  220V/380V/440V  and  the 
frequency  setting  for  50/60HZ  is  show  in  figure7. 
Please check the voltage/frequency selector setting 
is correct before start the generator. 

CAUTION :   

THE  GENERATOR  OR  AVR  MAY  BE  DAMAGED 
IF  THE  VOLTAGE  /  FREQUENCY  SELECTOR 
SETTING IS INCORRECT. 

UFRO DIP:   
Close - please refer to solid curre in Figure8. 
Open - please refer to dotted curre in Figure8. 

All manuals and user guides at all-guides.com

Summary of Contents for EA05A

Page 1: ...1 Chien Fu ST Chyan Jenn Dist Kaohsiung TAIWAN Tel 886 7 8121771 Fax 886 7 8121775 URL http www kutai com tw Email service mail kutai com tw Self Excited Automatic Voltage Regulator 5 Amp AVR For General Generators All manuals and user guides at all guides com a l l g u i d e s c o m ...

Page 2: ...g N phase as the detective input It will also cause the voltage imbalance EA05A can improve the above situation and increase the generator s rated voltage usage space such as 380V 440V We can all detect by the phase voltage 1 When the rated phase voltage of the generator is 220VAC the input terminals B C and sensing terminals A C can join together as show as figure3 It s the original setting or co...

Page 3: ...e source 2 Allow approximately 3 seconds before removing the DC source 3 With the voltage regulator disconnected wires 3 and 4 start the prime mover and measure the residual voltage available at the auxiliary winding If this voltage is greater than 5 Vac reconnect voltage regulator and voltage build up should be successful If less than 5 Vac is measured repeat field flashing procedure 4 If repeati...

Page 4: ...DIP 1000 OHM EXT VR Frequency Selector Volt Field G 380V 60HZ 380V 50HZ STAB U F 3 2 1 ON VOLT C 3 2 1 ON B F F A ON R T S N 3 1 2 UFRO DIP 1000 OHM EXT VR Frequency Selector Volt Field 220V 60HZ 220V 50HZ 2 1 3 ON 2 1 3 ON STAB U F VOLT B C F F A R T S N 3 ON 1 2 G UFRO DIP 1000 OHM EXT VR Frequency Selector Volt Figure 1 Figure 2 Figure 3 Figure 4 UFRO DIP All manuals and user guides at all guid...

Page 5: ... 5 Flash with Battery Figure 6 Figure 7 Figure 8 Figure 9 GENERATOR OUTPUT VOLTAGE GENERATOR OUTPUT VOLTAGE SOFT START V Sec 1 0 FREQUENCY HZ 10 20 40 30 50 60 0 2 60HZ OF MONINAL 80 20 40 60 50HZ 120 100 OF MONINAL 80 20 40 60 120 100 3 2 1 Field ON 440V 60HZ 440V 50HZ ON 1 1 STAB U F 3 2 VOLT C B 3 2 A F F ON R T S N G UFRO DIP 1000 OHM EXT VR Frequency Selector Volt All manuals and user guides ...

Reviews: