
4 Installation
Kübler Group
54 - EN
BA Sendix® 58xxFS2 / 58xxFS3 - R60049.0009 - 04
4.1.5 Cable Routing
NOTICE
Cable Routing
Route the sensor cable free of any tension, so that no addi-
tional force is applied on the measuring system. Consider the
minimum bending radii of the connection cable.
Comply with the instructions in chapter
Information for EMC-Compliant Installation [
Wiring
When wiring the facility, pay attention to proper cable routing.
• Separate the wiring into power groups such as motor/power
supply lines and signal and data lines.
• Route the signal and data lines as close as possible to
ground surfaces (frames, metal rails, cabinet sides) and not
parallel to motor and power supply lines or other lines carry-
ing high interference levels.
• Do not connect other users with high interference levels
(such as frequency converters, solenoid valves, contactors)
to the power supply of the device.
4.1.5.1 Cable Bending Radius
R
min
ø d
52104843
The following minimum values apply for encoders with cable
outlet (R
min
):
R
min
Fixed installation
75 [2.95]
Flexible use
110 [4.33]
4.2 Electrical Installation
4.2.1 General Information for the Connection
ATTENTION
Destruction of the device
Before connecting or disconnecting the signal cable, always
disconnect the power supply and secure it against switching
on again.
Summary of Contents for Sendix 58 FS2 Series
Page 2: ...Deutsch 3 English 35 Fran ais 65 Italiano 97 Espa ol 129...
Page 161: ...Notizen Notes...
Page 162: ......
Page 163: ......