36
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control via
the internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add
NetFeeler Lite to detect temperature, humidity, smoke and security sensors. Thus, making NetAgent
II a versatile management tool. NetAgent II also supports multiple languages and is setup for
web-based auto language detection.
Typical topology of the UPS Network Management
Relay card
A 10-pin terminal is supported to offer the signals of Bypass, Utility Failure, Inverter On, Battery
Low, UPS fault, UPS Alarm, and UPS Shutdown.
The relay communication card contains six dry contact outputs and one dry input. The inputs and
outputs are factory programmed according to functions listed in the table
Table: Relay Contacts (communication card)
Pin
Function Description
Input or Output
1 Utility
Failure
Output
2
Battery Low
3
4 Bypass
On
5 UPS
Fault
6 Inverter
On
7 Summary
Alarm
8 common
9
Remote Sh
Input (5~12V)