32
4.4.13 Parallel quantity setting
Parallel quantity setting (Note: Inside the broken-line is the flashing part.)
When under the parallel ID setting press “ON” or when under parallel redundancy quantity
setting press “OFF”, it goes to the parallel quantity setting. The parallel quantity flashes as in above
picture.
①
Use button “
” to set the parallel quantity. The parallel quantity range is 2~4.
②
Press “ON”
to exit the parallel quantity setting and save the parallel quantity setting value and goes to parallel
redundancy quantity setting.
③
Press “OFF” to exit the parallel quantity setting and goes to parallel
ID setting.
4.4.14 Parallel redundancy quantity setting
Parallel redundancy quantity setting (Note: Inside the broken-line is the flashing part.)
When under the parallel quantity setting press “ON”, it goes to the parallel redundancy quantity
setting. The parallel redundancy quantity flashes as in above picture.
①
Use button “
” to set the
parallel redundancy quantity. The parallel redundancy quantity range is 0~3.
②
press “ON” to exit the
mode setting and save the mode setting value and then UPS LCD panel setting is accomplished.
③
Press “OFF” to go to parallel quantity setting.