30
4.4.9 Periodical battery self-test Setting
Periodical battery self-test setting (note: the part in dashed box flashes)
In the buzzer setting press “ON” or in parallel ID setting press “OFF”, it goes to the battery
self-test setting. In the meantime the setting state flashes as above picture shows (Note: ON 1- the
battery self-test function is enabled, UPS will do self-test 10 seconds every 30 days; ON 2- the
battery self-test function is enabled, UPS will do self-test 10 minutes every 30 days; ON 3- the battery
self-test function is enabled, UPS will do self-test till battery voltage reaches EOD point every 30 days;
OFF-battery self-test function is disabled.).
①
Press “
” to set periodically self-test setting. The
options are OFF, ON 1, ON 2 and ON 3.
②
Press “ON” to exit Periodically Self-test setting and save
the setting value, and goes to battery temperature compensation sensor switch setting.
③
Press
“OFF” to exit Periodically Self-test setting and goes to buzzer setting.
4.4.10 Battery temperature compensation sensor switch setting
Battery temperature compensation sensor switch setting
(Note: the information in the red box will be flashing)
Press “ON” under the periodical battery self-test setting or press “OFF” under device address
setting, goes to the battery temperature compensation switch setting. The setting state flashes as
above picture shows (Note: OFF means turn off the sensor switch, ON means turn on the sensor
switch, send query command to sensor with address 11,12 every second.
①
Press “
” is to set the
battery sensor, with options OFF & ON.
②
Press “ON” to exit the battery sensor setting and save
the battery sensor setting value and transfer to device address setting.
③
Press “OFF” to exit the
battery sensor setting and transfer to battery periodical battery self-test setting.