WARNING
Unintentional starting of pump set
Risk of injury by moving parts!
▷
Ensure that the pump set cannot be started up unintentionally.
▷
Always make sure the electrical connections are disconnected before carrying
out work on the pump set.
WARNING
Incorrect connection to the mains
Damage to the mains network, short circuit!
▷
Observe the technical specifications of the local energy supply companies.
1.
Check the available mains voltage against the data on the motor name plate.
2.
Select an appropriate start-up method.
NOTE
A motor protection device is recommended.
5.9.1
Earthing
DANGER
Electrostatic charging
Explosion hazard!
Fire hazard!
Damage to the pump set!
▷
Connect the PE conductor to the earthing terminal provided.
5.10 Checking the direction of rotation
DANGER
Temperature increase resulting from contact between rotating and stationary
components
Explosion hazard!
Damage to the pump set!
▷
Never check the direction of rotation by starting up the unfilled pump set.
▷
Separate the pump from the motor to check the direction of rotation.
DANGER
Rotating shaft during direction of rotation check
Risk of injury!
▷
Maintain a safe distance to the pump set.
▷
Comply with the general health and safety regulations.
CAUTION
Drive and pump running in the wrong direction of rotation
Damage to the pump!
▷
Refer to the arrow indicating the direction of rotation on the pump.
▷
Check the direction of rotation. If required, check the electrical connection and
correct the direction of rotation.
5 Installation at Site
38 of 94
Omega / Omega V