5 Installation at Site
5.1 Safety regulations
For all work involving assembly, reassembly and installation, observe the following
safety information:
DANGER
Improper installation in potentially explosive atmospheres
Explosion hazard!
Damage to the pump set!
▷
Comply with the applicable local explosion protection regulations.
▷
Observe the information in the data sheet and on the name plates of pump and
motor.
DANGER
Improper transport
Risk of injury from lifting heavy components!
▷
Select lifting accessories which are suitable for the component weight.
▷
Always use the attachment points provided for the lifting accessories.
▷
Comply with the applicable health and safety regulations.
5.2 Checks to be carried out prior to installation
Place of installation
WARNING
Installation on mounting surface which is unsecured and cannot support the load
Personal injury and damage to property!
▷
Use a concrete of compressive strength class C12/15 which meets the
requirements of exposure class XC1 to EN 206-1.
▷
The mounting surface must have set and must be completely horizontal and
even.
▷
Observe the weights indicated.
1.
Check the structural requirements.
All structural work required must have been prepared in accordance with the
dimensions stated in the outline drawing/general arrangement drawing.
5.3 Installing the pump set
WARNING
Hands or foreign objects inside the pump casing
Risk of injuries, damage to the pump!
▷
Check that the inside of the pump is free from any foreign objects. Remove any
foreign objects.
▷
Never insert your hands or any other objects into the pump, if the pump set has
not been disconnected from the power supply and secured against
unintentional start-up.
Depending on the type of installation, several instructions need to be carried out as
applicable:
▪
Prepare and install the base frame/support frame.
▪
Install the pump and motor on the prepared base frame/support frame.