7 Operation
43 of 68
Hyamat SVP Eco
Table 29:
Example of status of digital outputs (1-2-4-7). The following is reported via relay output 1: General fault
message (configurable)
Optional IO card
Standard
Digital output
R8
R7
R6
R5
R4
R3
DO2
D01
R2
R1
Bit pattern on
display
0
0
0
0
0
0
0
0
0
I
7.2.1.2.2 Menu: Diagnosis
In the Diagnosis section, the user is provided with information about faults and
warning messages that pertain to the pump set or process. The frequency inverter
can be in fault (standstill) or warning (operational) status. The user can also find
previous messages in the history.
Messages
All monitoring and protective functions trigger warnings or alerts. These are
signalled via the amber or red LED of the LED traffic light function.
A corresponding message is output on the control panel display. If more than one
message is output, the last one is displayed. Alerts have priority over warnings.
AUTO
17.48 m
³/h
4.62 bar
2893 rpm
W57
rpm
C M
RUN
Low flow
1
5
2
3
4
Fig. 15:
Message display
1
Name of the message displayed in the centre
2
Display of the master and login level
3
Display of the message: The most recently received message is displayed in
large format on the main screen. Three operating values are displayed in small
format.
4
Display of operating status
5
Displays the current operating mode
Pending messages
If a message has occurred and been acknowledged but has not gone, this message
will be listed in the Pending Messages menu. All current messages can be displayed in
the Diagnosis menu under Pending Messages (
2-1
). Active warnings and alerts can
also be connected to the relay outputs.
Message history
Only messages that have come, been acknowledged, and gone are listed in the
message history. The message history can be viewed by selecting the Message History
parameter
2-2
. The last 100 messages are listed here. You can use the arrow keys and
the OK key to select an entry from the list.
Acknowledging and resetting messages
NOTE
Depending on the combination of settings, the frequency inverter could
conceivably restart automatically after acknowledgement/reset or when the cause
of the malfunction or fault has been eliminated.