7 Operation
37 of 68
Hyamat SVP Eco
Message history
Only messages that have come, been acknowledged, and gone are listed in the
message history. The message history can be viewed by selecting the Message History
parameter
2-2
. The last 100 messages are listed here. You can use the arrow keys and
the OK key to select an entry from the list.
Acknowledging and resetting messages
NOTE
Depending on the combination of settings, the frequency inverter could
conceivably restart automatically after acknowledgement/reset or when the cause
of the malfunction or fault has been eliminated.
Acknowledgement
Messages can be acknowledged once the cause has been rectified. Messages can be
acknowledged individually in the Diagnosis menu. A message can also be
acknowledged via a digital input. Digital input 2 is defaulted for this purpose.
Overview of warnings and alerts
Messages can be acknowledged as follows:
Table 19:
Acknowledgement types for messages
Property of message
Type of acknowledgement
Self-acknowledging
Message is automatically acknowledged if condition for message no longer applies.
Automatic
acknowledgement
(configurable)
Users can choose between automatic acknowledgement and manual
acknowledgement.
Partially automatic
acknowledgement
Alerts that are partially acknowledged automatically carry out automatic
acknowledgement in increasingly large intervals after the alert condition no longer
applies. If the alert occurs repeatedly within a specific time window, automatic
acknowledgement is suspended.
As soon as the alarm condition of a pending alert no longer exists, the time interval is
started. When this interval expires, automatic acknowledgement takes place.
If the alert occurs again within 30 seconds after the time interval has started, the
interval is extended by one increment. Should this not be the case, the previous
(shorter) time interval is reverted to and corresponding action is taken again in
30 seconds. The time intervals are 1 second, 5 seconds, 20 seconds, and endless (i.e.
manual acknowledgement is required). When the 20-second interval is extended,
automatic acknowledgement no longer takes place.
No automatic
acknowledgement
Must be acknowledged manually.
Time stamp
If a message is not acknowledged and its condition comes and goes several times in
this time window, the first occurrence of the message is always used for the Message
Come time stamp. The Message Condition Gone time stamp, however, always shows
the last time the message condition was no longer active.
7.1.1.3.3 Menu: Settings
General settings can be made or the settings for the process optimised in the Settings
section.
Locking operating keys
Table 20:
Parameters for setting the control panel
Parameter
Description
Possible settings
Factory setting
3-1-2-2
Control Keys Require Login
The MAN, OFF, AUTO and FUNC keys are
locked without a valid login (customer).
▪
0 = OFF
▪
1 = ON
0 = OFF
Locking operating keys
The operating keys of the control panel can be locked via the
3-1-2-2
parameter to
prevent unauthorised operation or unauthorised acknowledgement of alerts.