Commissioning Guide for VPQ-2

Page: 4 of 10

Rules

1.  Each power pack will power up (12) diffusers. It has (2) outlets; you may daisy-chain up to (6) diffusers per outlet. 

The last diffuser in each run must have a termination plug installed. Every diffuser connected to a power pack is 

part of the power pack’s local network.

2.  A USB module or MCM is REQUIRED if any diffuser is to be configured as a slave. If all diffusers are masters, 

they can be configured with the thermostat.

3.  A “loop” is defined as a thermostat and any diffusers it is connecting; master or slave.

4.  The master diffuser is the unit to which the thermostat is connected.

5.  Without an MCM, any diffuser loop is limited to (12) diffusers. This means that you may have (1) thermostat which 

controls (1) master diffuser and (11) slave diffusers, all connected to the same power pack. The MCM can connect 

to up to (4) power packs, which will allow any diffuser network to be expanded to (48) units.

6.  The MCM may be addressed via an IP address for easy diffuser network programming.

VPQ Diffuser

VPQ Diffuser

VPQ Diffuser

VPQ Diffuser

VPQ Diffuser

VPQ Diffuser

Power Module

Power Module

Wall

Thermostat

Wall

Thermostat

Laptop

MCM

4-pin

4-pin

4-pin

4-pin

4-pin

4-pin

RJ-12

RJ-12

Wiring Options

Typical MCM Network

USB Module

RJ-9

RJ-9

RJ-9

USB Cable

Summary of Contents for VPQ-2

Page 1: ...eries diffusers We have captured as much pertinent information as possible to provide a thorough overview on how to setup install and operate the VPQ 2 Information is subject to change at anytime with...

Page 2: ...diffuser and power pack to diffuser Power Pack Module which will provide power to the VPQ 2 Master Communications Module MCM Allows for large diffuser networks and integration with BACnet and LONworks...

Page 3: ...ruegerinfo krueger hvac com www krueger hvac com Wiring Options Single Primary Diffuser Daisy Chain Primary and Secondary VPQ Diffuser VPQ Diffuser VPQ Diffuser Laptop Power Module 4 pin 4 pin 4 pin R...

Page 4: ...as a thermostat and any diffusers it is connecting master or slave 4 The master diffuser is the unit to which the thermostat is connected 5 Without an MCM any diffuser loop is limited to 12 diffusers...

Page 5: ...Navigate there and double click to run the exesetup file Follow the on screen instructions for the MLMServer setup until your installation is complete Once your installation is complete and if you ar...

Page 6: ...After sync is complete you will see warning messages indicating new nodes close the window Here is an example of the finished setup Initial Power Up Motors run full open to full close for calibration...

Page 7: ...terminal resistor in place The loops should start with the number one and increment two three four etc In the Loop Number field enter the number one and press the Write button When loop changes are ma...

Page 8: ...the diffuser with temperatures above the device You will see two folders on the left Click the one labeled Type 7 Check the loop number and ensure it matches the value of the diffuser previously setu...

Page 9: ...Commissioning Guide for VPQ 2 Page 9 of 10 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com Notes...

Page 10: ...Information Learn More About Other Krueger Air Distribution Solutions Krueger continues to lead the industry in the development of innovative products and air distribution solutions To learn more abo...

Reviews: