Commissioning Guide for VPQ-2

Page: 2 of 10

Components

USB Module

: Allows a 

laptop to communicate with 

the diffuser network for 

programming.

NOTE: Each VPQ-2 diffuser will come with a 4-pin cable. The thermostat option will include the 6-pin RJ12 cable. 

The USB module and MCM will include the 4-pin RJ9 cable. All cables are 25’ standard. 75’ cables are available as 

parts.

6-pin RJ12 Cable

: This cable 

connects the thermostat to 

the diffuser. 

Thermostat

: Digital 

thermostat used to control 

either a single diffuser or a 

network of diffusers.

4-pin Cable

: This cable 

carries power and signal from 

diffuser to diffuser and power 

pack to diffuser.

Power Pack

: Module which 

will provide power to the 

VPQ-2.

Master Communications 

Module (MCM)

: Allows for 

large diffuser networks and 

integration with BACnet and 

LONworks. This takes the 

place of the USB module.

VPQ-2

: Digitally controlled 

VAV diffuser with plaque 

face, which includes its own 

communication module. 

There is no physical 

difference between a master 

and slave diffuser.

4-pin RJ9 Cable

: This cable 

connects the USB module to 

the diffuser network via the 

power pack OR diffuser.

Termination Plug

: Small, 

4-pin plug which electrically 

signals the end of a diffuser 

chain. Shipped installed in 

each diffuser and power 

pack.

The purpose of this document is to serve as a 

guide for Krueger’s VPQ-2 diffusers. It will cover all 

components and setup parameters for the digital VAV 

system.

For additional questions or assistance, please contact 

us at [email protected].

Summary of Contents for VPQ-2

Page 1: ...eries diffusers We have captured as much pertinent information as possible to provide a thorough overview on how to setup install and operate the VPQ 2 Information is subject to change at anytime with...

Page 2: ...diffuser and power pack to diffuser Power Pack Module which will provide power to the VPQ 2 Master Communications Module MCM Allows for large diffuser networks and integration with BACnet and LONworks...

Page 3: ...ruegerinfo krueger hvac com www krueger hvac com Wiring Options Single Primary Diffuser Daisy Chain Primary and Secondary VPQ Diffuser VPQ Diffuser VPQ Diffuser Laptop Power Module 4 pin 4 pin 4 pin R...

Page 4: ...as a thermostat and any diffusers it is connecting master or slave 4 The master diffuser is the unit to which the thermostat is connected 5 Without an MCM any diffuser loop is limited to 12 diffusers...

Page 5: ...Navigate there and double click to run the exesetup file Follow the on screen instructions for the MLMServer setup until your installation is complete Once your installation is complete and if you ar...

Page 6: ...After sync is complete you will see warning messages indicating new nodes close the window Here is an example of the finished setup Initial Power Up Motors run full open to full close for calibration...

Page 7: ...terminal resistor in place The loops should start with the number one and increment two three four etc In the Loop Number field enter the number one and press the Write button When loop changes are ma...

Page 8: ...the diffuser with temperatures above the device You will see two folders on the left Click the one labeled Type 7 Check the loop number and ensure it matches the value of the diffuser previously setu...

Page 9: ...Commissioning Guide for VPQ 2 Page 9 of 10 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com Notes...

Page 10: ...Information Learn More About Other Krueger Air Distribution Solutions Krueger continues to lead the industry in the development of innovative products and air distribution solutions To learn more abo...

Reviews: