Commissioning Guide for VPQ-2
Page: 8 of 10
Motor Settings
»
Click on the diffuser you wish to adjust.
»
Click the folder labeled “
Type 10
” on the left and
expand the “
Process
” folder.
»
Click “
Motor Min
” and enter desired motor minimum
percentage, 0-100.
See Figure 4 below.
- You may also set a motor maximum percentage.
Thermostat Settings
»
Click the diffuser with temperatures above the device.
»
You will see two folders on the left. Click the one
labeled “
Type 7
”.
»
Check the loop number and ensure it matches the
value of the diffuser previously setup.
»
Click the “
Process
” tab; you can adjust your setpoint
and setpoint limits. Remember to click “
Write
” after
any changes.
See Figures 1 and 2 below.
- To maximize the range of operation enter, a high delta
between your max and min setpoint limits.
»
Click the “
Setup
” folder and click “
Edit Mode
”, place
a check mark in the “
Setup Menu Enable
” only; click
“
Write
”.
See Figure 3 below.