Commissioning Guide for VPQ-2
Page: 7 of 10
Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | [email protected] | www.krueger-hvac.com
Here are a few examples of the finished setup.
Multiple Loop Operation
»
In the “
Physical
” tab, click a diffuser and navigate to
“
Identification
”, then “
Loop Number
”.
- Each loop is defined as a zone.
- Each zone is controlled by a single thermostat.
- The last diffuser in the daisy chain must have the terminal
resistor in place.
»
The loops should start with the number one and
increment, two, three, four, etc.
- In the “
Loop Number
” field, enter the number one and
press the “
Write
” button.
- When loop changes are made to the diffuser, any
attached thermostat will follow suit.
»
Repeat the process for all connected diffusers and
designate loops as required.
- Remember, you cannot have more than one thermostat
per loop.
- After you have entered all of your loop designations,
press the “
Sync
” button.
- After sync is complete, you will see warning messages
indicating new nodes; close the window.
Diffuser Commissioning & Setup (Continued)
»
Continue to thermostat settings.