40
Fan Powered Terminal Units IOM
Set
Point
CFM
MANUAL %
Display
(option 6)
REMOTE 0-10Vdc (0-20mA)
DC Signal (option 7)
REMOTE 2-10Vdc (4-20mA)
DC Signal (option 8)
885
100
10
(20.0)
10
(20.0)
877
99
9.9
(19.8)
9.9
(19.8)
868
98
9.8
(19.6)
9.8
(19.7)
859
97
9.7
(19.4)
9.8
(19.5)
850
96
9.6
(19.2)
9.7
(19.4)
841
95
9.5
(19.0)
9.6
(19.2)
832
94
9.4
(18.8)
9.5
(19.0)
824
93
9.3
(18.6)
9.4
(18.9)
815
92
9.2
(18.4)
9.4
(18.7)
806
91
9.1
(18.2)
9.3
(18.6)
797
90
9.0
(18.0)
9.2
(18.4)
788
89
8.9
(17.8)
9.1
(18.2)
779
88
8.8
(17.6)
9.0
(18.1)
770
87
8.7
(17.4)
9.0
(17.9)
762
86
8.6
(17.2)
8.9
(17.8)
753
85
8.5
(17.0)
8.8
(17.6)
744
84
8.4
(16.8)
8.7
(17.4)
735
83
8.3
(16.6)
8.6
(17.3)
726
82
8.2
(16.4)
8.6
(17.1)
717
81
8.1
(16.2)
8.5
(17.0)
708
80
8.0
(16.0)
8.4
(16.8)
700
79
7.9
(15.8)
8.3
(16.6)
691
78
7.8
(15.6)
8.2
(16.5)
682
77
7.7
(15.4)
8.2
(16.3)
673
76
7.6
(15.2)
8.1
(16.2)
664
75
7.5
(15.0)
8.0
(16.0)
655
74
7.4
(14.8)
7.9
(15.8)
647
73
7.3
(14.6)
7.8
(15.7)
638
72
7.2
(14.2)
7.8
(15.5)
629
71
7.1
(14.0)
7.7
(15.4)
620
70
7.0
(13.8)
7.6
(15.2)
611
69
6.9
(13.6)
7.5
(15.0)
602
68
6.8
(13.6)
7.4
(14.9)
593
67
6.7
(13.4)
7.4
(14.7)
585
66
6.6
(13.2)
7.3
(14.6)
576
65
6.5
(13.0)
7.2
(14.4)
567
64
6.4
(12.8)
7.1
(14.2)
558
63
6.3
(12.6)
7.0
(14.1)
549
62
6.2
(12.4)
7.0
(13.9)
540
61
6.1
(12.2)
6.9
(13.8)
531
60
6.0
(12.0)
6.8
(13.6)
523
59
5.9
(11.8)
6.7
(13.4)
514
58
5.8
(11.6)
6.6
(13.3)
505
57
5.7
(11.4)
6.6
(13.1)
496
56
5.6
(11.2)
6.5
(13.0)
487
55
5.5
(11.0)
6.4
(12.8)
478
54
5.4
(10.8)
6.3
(12.6)
470
53
5.3
(10.6)
6.2
(12.5)
461
52
5.2
(10.4)
6.2
(12.3)
452
51
5.1
(10.2)
6.1
(12.2)
Set
Point
CFM
MANUAL %
Display
(option 6)
REMOTE 0-10Vdc (0-20mA)
DC Signal (option 7)
REMOTE 2-10Vdc (4-20mA)
DC Signal (option 8)
443
50
5
(10.0)
6.0
(12.0)
434
49
4.9
(9.8)
5.9
(11.8)
425
48
4.8
(9.6)
5.8
(11.7)
416
47
4.7
(9.4)
5.8
(11.5)
408
46
4.6
(9.2)
5.7
(11.4)
399
45
4.5
(9.0)
5.6
(11.2)
390
44
4.4
(8.8)
5.5
(11.0)
381
43
4.3
(8.6)
5.4
(10.9)
372
42
4.2
(8.4)
5.4
(10.7)
363
41
4.1
(8.2)
5.3
(10.6)
354
40
4
(8.0)
5.2
(10.4)
346
39
3.9
(7.8)
5.1
(10.2)
337
38
3.8
(7.6)
5.0
(10.1)
328
37
3.7
(7.4)
5.0
(9.9)
319
36
3.6
(7.2)
4.9
(9.8)
310
35
3.5
(7.0)
4.8
(9.6)
301
34
3.4
(6.8)
4.7
(9.4)
293
33
3.3
(6.6)
4.6
(9.3)
284
32
3.2
(6.4)
4.6
(9.1)
275
31
3.1
(6.2)
4.5
(9.0)
266
30
3
(6.0)
4.4
(8.8)
257
29
2.9
(5.8)
4.2
(8.6)
248
28
2.8
(5.6)
4.2
(8.5)
239
27
2.7
(5.4)
4.1
(8.3)
231
26
2.6
(5.2)
4.0
(8.2)
222
25
2.5
(5.0)
3.9
(8.0)
213
24
2.4
(4.8)
3.8
(7.8)
204
23
2.3
(4.6)
3.8
(7.7)
195
22
2.2
(4.4)
3.6
(7.5)
186
21
2.1
(4.2)
3.7
(7.4)
177
20
2
(4.0)
3.6
(7.2)
169
19
1.9
(3.8)
3.5
(7.0)
160
18
1.8
(3.6)
3.4
(6.9)
151
17
1.7
(3.4)
3.4
(6.7)
142
16
1.6
(3.2)
3.3
(6.6)
133
15
1.5
(3.0)
3.2
(6.4)
124
14
1.4
(2.8)
3.1
(6.2)
116
13
1.3
(2.6)
3.0
(6.1)
107
12
1.2
(2.4)
3.0
(5.9)
98
11
1.1
(2.2)
2.9
(5.8)
89
10
1
(2.0)
2.8
(5.6)
80
9
0.9
(1.8)
2.7
(5.4)
71
8
0.8
(1.6)
2.6
(5.3)
62
7
0.7
(1.4)
2.6
(5.1)
54
6
0.6
(1.2)
2.5
(5.0)
45
5
0.5
(1.0)
2.4
(4.8)
36
4
0.4
(0.8)
2.3
(4.6)
27
3
0.3
(0.6)
2.2
(4.5)
18
2
0.2
(0.4)
2.2
(4.3)
9
1
0.1
(0.2)
2.1
(4.2)
CFM VALUES BELOW RECOMMENDED MINIMUM MAY AFFECT LIFE OF MOTOR.
TABLE 32: KLPP Size 4 ECM CALIBRATION
Summary of Contents for KLPP
Page 49: ......