background image

Krueger | 1401 N Plano Rd | Richardson, TX 75081 | 972.680.9136 | [email protected] | www.krueger-hvac.com

Installation, Operation, & Maintenance for CRFF-E Series

 

Page: 

7

 of 

2

6

Control Modes 

The ENV1028 operates in one of three selectable modes. 

The Mode is selected using the control DIP switch; MANUAL 

control  (on-board  potentiometer),  ANALOG  control 

(Remote 0-10 VDC), NETWORK control (MODBUS RTU). 

The ENV1028 is shipped from the factory in NETWORK 

control mode.

Manual Control Mode

In Manual control mode, the motor speed is set using the 

onboard potentiometer. Onboard potentiometer rotation is 

CW to increase the motor output.

Analog Control Mode

In ANALOG control mode, the motor output is set using an 

external 0-10 VDC demand signal.

Networ

k

 Control Mode

In NETWORK control mode, the motor output is set using 

MODBUS Register 2. Motor output is specified as a value 

from 0 to 100 representing a percentage of motor torque 

output. Each ENV1028 in a MODBUS network must be 

set to a unique address. The address value is set in 

binary using the eight DIP switches of switch band (S2). 

A maximum of 200 ENV1028 devices is recommended 

per local area network (LAN). 

Networ

k

kControl Mode (cont)

I

f  a  Krueger  ACC  Control  Console  is  the  MODBUS 

master,  then  addresses  should  be  assigned  within  the 

address  range  supported  by  the  Control  Console. 

Address  zero  should  not  be  used  as  it is reserved for 

global  commands.  Address  switch  settings  are  only 

checked  by  the  ENV1028  at  power-up.  Power must be 

cycled (OFF/ON) before any changes take effect.

Registers relevant to this mode:

1

ON

ADE02

2

1       3 4  5 6  7 8

O

N

2

1

ON

ADE02

2

1       3 4  5 6  7 8

O

N

2

Manual Mode = 1 OFF 2 OFF

Analog Mode = 1 ON 2 OFF

Note: Network mode can be configured using either DIP switch setting shown 

above. DIP switch pictorials are for reference and may be labeled differently by 

the manufacturer.

1

ON

ADE02

2

1       3 4  5 6  7 8

O

N

2

Network Mode = 1 OFF 2 ON

1

ON

ADE02

2

1       3 4  5 6  7 8

O

N

2

Network Mode = 1 ON 2 ON

Register 1 “Start/Stop” (R/W)

To enable motor, write a value of 1; To disable

motor, write a value of 0

Register 2 “Motor Set Speed” (R/W)

Motor Target speed value. Values may be written

from 0 to 100

Register 6 “RPM” (R)

Motor RPM. Read from the motor

Register 12 “Actual Motor Speed Instruction” (R)

Speed control signal applied to the motor by the

ENV1028. (R/W) = Read/Write, (R) = Read Only

Summary of Contents for CRFF-E

Page 1: ...INSTALLATION OPERATION MAINTENANCE Fan Filter Units CRFF E CRFF E ARS CRFF E ARSM ECM Motors Revision 02 01 17...

Page 2: ...m 13 Service Removal and Replacement of CRFF E filters 14 Service Removal and Replacement of Roomside Replaceable Filters 15 Service CRFF E CRFF E ARS Motor Removal and Installation 16 Service CRFF E...

Page 3: ...on is located on the product and serial number labels located adjacent to the electrical box If you cannot locate the FO please contact Krueger for this information Read and Save These Instructions To...

Page 4: ...onto the gasketed grid If using a flexible grid typically supported with wires the unit must be secured to an overhead structure with eyebolts s hooks and chain Screw the four eyebolts into the nutser...

Page 5: ...ed between 0 50 in wc and 3 00 in wc by turning the set screw accessible for the front of the control enclosure Counterclockwise rotation will increase the set point differential for switching clockwi...

Page 6: ...Consoles using MODBUS RTU Additional details of the controls modes are provided on page 7 FEATURES Networkable Via MODBUS RTU 0 10 VDC Analog Control Manual Control Via Onboard Potentiometer Simple C...

Page 7: ...band S2 A maximum of 200 ENV1028 devices is recommended per local area network LAN NetworkkControl Mode cont If a Krueger ACC Control Console is the MODBUS master then addresses should be assigned wi...

Page 8: ...fo krueger hvac com www krueger hvac com Control Modes continued Example of binary S2 switch settings 5 6 1 2 3 4 8 7 ON DIP 1 1 2 3 4 5 6 7 8 ON DIP 11 1 2 4 3 5 6 8 7 ON DIP 21 3 1 2 4 5 6 7 8 ON DI...

Page 9: ...S Test Probe Jack Points The test probe jacks may be used to measure the motor rpm or the PWM signal that is being output to the motor In Manual or Analog Control Mode with an Address setting of 1 or...

Page 10: ...eset non volatile registers to factory default values write 170 AA hex to Register 14 then cycle power Note Register 24 may be read in network mode to determine the value of 0 10VDC signal that may be...

Page 11: ...e Contamination Warranty Please reference the Krueger website for Warranty information located in the Terms and Conditions of Sales document or click on the following link http www krueger hvac com pd...

Page 12: ...lashes 3 longs then an extra lon A flow index of 04 flashes an extra long then 4 shor A flow index of 100 flashes 10 longs then an extra lon Use the ON OFF button to turn the motor on or off Point the...

Page 13: ...lte remove the ceiling panel next to the unit if applicable Switch the ON OFF switch to the OFF position Remove the prefilter from the snap in frame See Figure 1 Clean the prefilter by hand washing in...

Page 14: ...ly off the HEPA ULPA filter See Figure 1 Remove filter deflectors using 5 32 drill bit Keep filter deflectors to install in new filter Discard the used filter as per requirements of the applicable reg...

Page 15: ...ll the filter slowly away from the seal so that the gel remains in the filter gel track 3 Carefully clean plenum assembly knife edge surface of residual gel material 4 Inspect filter for visible damag...

Page 16: ...ter 6 Disconnect 5 pin and 16 pin wire harnesses from the electrical box housing and remove tubing for test port if installed 7 Remove the eight mounting screws to free the motor blower assembly from...

Page 17: ...ews that secure the venturi ring to the bottom face of the lid 4 Using a 5 32 0 40 cm Allen wrench remove the blower wheel from the motor shaft Remove motor from the venturi ring by removing the three...

Page 18: ...dec PerfectSpeed When you order a replacement motor they will be a form and fit replacement except for the cable that connects to the control board and the motor The new Nidec motor will require you t...

Page 19: ...the potential to starve or over feed the fan with air causing the motor to stall which can damage the fan motor This also can be minimized by notifying Titus beforehand for assistance The ECM motors...

Page 20: ...age 20 of 26 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com Universal Card Wiring Diagram 4 pin Control Cable 5 pin Power Cable 4 Pin MTA Mo...

Page 21: ...com Wiring Diagrams continued Universal Card Wiring Diagram w Continous Filter Monitoring 4 pin Control Cable 5 pin Power Cable 4 Pin MTA Motor Connector Remote Run Indicator LED Note Register 24 may...

Page 22: ...nance for CRFF E Series Page 22 of 26 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com Wiring Diagrams continued Infrared Speed Control Remote...

Page 23: ...64 N A Universal Control Card CRFF E CRFF E ARS CRFF E ARSM 265888 N A Visual Speed Control Card CRFF E CRFF E ARS CRFF E ARSM 63951 002 N A IR Sensor Harness 63759 001 N A IR Sensor without Harness 6...

Page 24: ...Installation Operation Maintenance for CRFF E Series Page 24 of 26 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com CRFF E Filter Drawing...

Page 25: ...tion Operation Maintenance for CRFF E Series Page 25 of 26 Krueger 1401 N Plano Rd Richardson TX 75081 972 680 9136 kruegerinfo krueger hvac com www krueger hvac com CRFF E ARS and CRFF E ARSM Filter...

Page 26: ...specified performance along with air velocity measurement and adjustment tests No DOP is used on CRFF E series filters unless requested Recommended Testing All units that are airflow tested at Krueger...

Page 27: ......

Reviews: