3
ELECTRICAL CONNECTIONS
24
OPTIFLEX 2200 C/F
www.krohne.com
03/2019 - 4005066003 - AD NEPSI OPTIFLEX2200 R03 en
3.6.2 How to connect the electrical cables
Cable glands are supplied on customer demand. If you supply the cable glands, this part must
have a degree of ingress protection IP
≥
6X (IEC 60529).
•
Do not remove more than 6 mm / 0.2
¨
of insulation from the wire.
•
Connect the load resistor to the positive terminal of the power supply
•
Ground the negative connection.
•
If the load resistor has to be connected to the negative terminal, the loop resistance must not
be more than 350 ohms.
3.6.3 Supply voltage
Level transmitter with the 4...20 mA output option
Level transmitter with the PROFIBUS PA or FOUNDATION fieldbus output option
For more data, refer to
Maximum intrinsically-safe values for the electrical circuit
on page 21.
3.6.4 Electrical schematic
WARNING!
Use only Ex d-approved cable glands and plugs for Ex d applications. Use only Ex t-approved
cable glands and plugs for Ex t applications.
Do not remove more than 6 mm / 0.2
¨
of insulation from the wire.
CAUTION!
4...20 mA passive - HART output option:
4...20 mA passive - HART output option:
4...20 mA passive - HART output option:
4...20 mA passive - HART output option: Do not ground the positive connection.
Minimum voltage at
output terminals [V DC]
Maximum voltage at
output terminals [V DC]
Current output terminals
13.5
1
36
1
1
For a current output of 22 mA
Minimum voltage at
output terminals [V DC]
Maximum voltage at
output terminals [V DC]
Output terminals
Entity
9
24
FISCO
9
17.5
DANGER!
Keep the grounding wire a minimum distance of 2 mm / 0.83
¨
away from the output terminal.
CAUTION!
Make sure that you connect the load resistor to the positive side.