4.14 Diagnosis
4.14.1 Diagnosis 1
4.14.2 Diagnosis 2
Bit
Description
Recommended action
0
Flow Out Of Range
Check process conditions.
1
Velocity Out Of Range
Check process conditions.
2
Process Temperature Out Of
Range
Check process conditions.
3
Density Over Range
Check process conditions.
4
Electronics Temperature Out Of
Specification
Move electronics away from process influences. Protect the
electronics against direct sunlight.
5
Hardware Failure
Perform a power reset. If the status returns, contact manufacturer.
6
Memory Failure
Perform a power reset. If the status returns, contact manufacturer.
7
Sensor Error
Check cabling in case of remote device or replace sensor.
Table 4-28: Diagnosis 1
Bit
Description
Recommended action
0
Temperature or strain sensor
defective
Check cabling in case of remote device or replace sensor.
1
Data Error
Check process input configuration or reset to factory configuration.
2
No Sensor Signal
Check process conditions (entrained gas, viscosity). In case of remote
sensor check sensor cabling. Check internal sensor connections.
3
Sensor Signal Low
Check for entrained gas or viscosity of product.
4
2 Phase Flow Over Threshold
Check process for entrained gas.
5
Density Calibration Invalid
Restart density calibration, check product and operation mode or
reset to factory settings.
6
PROFINET Startup records
invalid
Check start-up records.
Note: Some parameters are scaled by a configurable unit within the
Note: Some parameters are scaled by a configurable unit within the
Note: Some parameters are scaled by a configurable unit within the
Note: Some parameters are scaled by a configurable unit within the
start-up records. Changing those units requires adjustment of the
start-up records. Changing those units requires adjustment of the
start-up records. Changing those units requires adjustment of the
start-up records. Changing those units requires adjustment of the
affected parameters.
affected parameters.
affected parameters.
affected parameters.
E.g. if density unit (ID 53) changes, the values of parameters ID 10,
ID 15 and ID 16 must be converted to the new unit manually.
7
Reserved
-
Table 4-29: Diagnosis 2