IFC090, IFC090 i with FF
IFC090-FF Configuration
IFC090 FF 01/2005
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5
D-47058 Duisburg
Tel.: 0203-301 309
Fax: 0203-301389 · E-mail: [email protected]
INTEG_OPTS
Description if enabled (i.e set to true)
Use Uncertain
Input values of
IN_1
or
IN_2
are also used for the integration, if their status are
Uncertain
. The calculation of
RTOTAL
isn’t affected by this setting (i.e. the value
is used for the integration, but even though the input is interpreted as
Bad
and
added to
RTOTAL
).
Use Bad
Status of input values of
IN_1
or
IN_2
isn’t interpreted as
Bad
value in the
calculation of
RTOTAL
even if they’re really
Bad
.
NOTE:
This doesn’t mean, that the values of inputs with
Bad
status are used for the
integration! The last value with
Good
status is used further on!
Add zero if Bad
Instead of using the last value with
Good
status for integration, zero (0.0) is used,
if the status of the input of
IN_1
or
IN_2
is Bad.