Supplementary Documentation
Page 25 of 44
IFC090, IFC090 i with FF
IFC090-FF Block Description
IFC090 FF 01/2005
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5
D-47058 Duisburg
Tel.: 0203-301 309
Fax: 0203-301389 · E-mail: [email protected]
Parameter
Access
Description
OUT_PTRIP R/W
Second discrete output. OUT_PTRIP can be used within a control system, to
get a discrete indication, that a specified value of totalization is reached (e.g.
as indication to start closing a valve). The specified value to reach can be set
in parameter PRE_TRIP.
NOTE
:
If the totalization reaches
PRE_TRIP
,
OUT_PTRIP
is set to 255 (0xFF).
see also:
PRE_TRIP, OUT_TRIP
OUT_RANGE R
Display scaling of the output OUT. It has no effect on the block and is used
by downstream blocks or control system to get the unit of the totalization.
OUT_TRIP R/W
Second discrete output. OUT_TRIP can be used within a control system, to
get a discrete indication, that the specified value of totalization for resetting
(automatic reset is selected) is reached. The specified value to reach can be
set in parameter
TOTAL_SP
.
see also: TOTAL
_SP, OUT_PTRIP
OUTAGE_LIM R/W
Maximum tolerable time for power failure. Not used by the IFC090-FF
PCT_INCL R
Percentage of
BAD
and
Uncertain
net flow values used in conjunction with
GOOD_LIM
and
UNCERT_LIM
to determine the status of the output value
OUT
. It is calculated by the following equation:
PCT_INCL = 100 * (1 - (rtotal / atotal),
where
rtotal
is the portion of
BAD
and
Uncertain
net flows and
atotal
the
absolute value of all net flows.
see also:
GOOD_LIM, UNCERT_LIM
PRE_TRIP R/W
When integration is counting up (see
INTEG_TYPE
) and the totalization
value equals or exceeds (
TOTAL_SP
-
PRE_TRIP
) then the discrete output
OUT_PTRIP
is set to 0xFF.
If counting down and the value of
OUT
is equal to or less than
PRE_TRIP
,
the discrete output
OUT_PTRIP
is set to 0xFF.
see also:
OUT_PTRIP
PULSE_VAL1 R/W
PULSE_VAL1 specifies the factor by witch
IN_1
is to be multiplied if
IN_1
is
used as input of accumulated pulses (i.e.
‘Input 1 accumulate’
is set in
INTEG_OPTS
). In this respect,
IN_
1 will be converted according to the
following equation:
IN_1 = IN_1 * PULSE_VAL1
PULSE_VAL2 R/W
PULSE_VAL2 specifies the factor by witch
IN_2
is to be multiplied if
IN_2
is
used as input of accumulated pulses (i.e.
‘Input 1 accumulate’
is set in
INTEG_OPTS
). In this respect, IN_2 will be converted according to the
following equation:
IN_2 = IN_2 * PULSE_VAL2
RESET_CONFIRM R/W
RESET_CONFIRM can be used by control systems to confirm a reset event
report if
‘Confirm reset’
is set in
INTEG_OPTS
.
RESET_IN R/W
RESET_IN can be used by control systems to reset the totalization by an
external signal. By setting
'value'
to
'Reset'
(0x01) and a status of
GoodNC:NS:NL
, the integrator will be reset as if
OP_CMD_INT
was set to
'Reset'
.
see also:
OP_CMD_INT, INTEG_TYPE