 DEVICE DESCRIPTION 

2

5

DK32 DK34

www.krohne.com

04/2015 - 4000422303  AD DK32/34 II2G R03 en

2.4  Flammable products

Atmospheric conditions:

Atmospheric conditions:

Atmospheric conditions:

Atmospheric conditions:

An explosive atmosphere is a mixture of air and flammable gases, vapours, mists or dusts under 
atmospheric conditions. It is defined by the following values T

atm

 = -20...+60

°

C /

-4...+140

°

F and P

atm

 = 0.8...1.1 bar. Outside of this range, for most mixtures no key figures are 

available for the ignition behaviour.

Operating conditions:

Operating conditions:

Operating conditions:

Operating conditions:

Variable area flowmeters operate outside of atmospheric conditions, which means that 
explosion protection according to directive 94/9/EC (ATEX) 

 regardless of the zone assignment 

 is fundamentally not applicable due to the lack of key safety data for the interior of the 

measuring section.

2.5  Equipment category

The flowmeters are designed in Category II 2G according to EN 60079-0 and EN 60079-11 for use 
in Zone 1.

2.6  Types of protection

The variable-area flowmeter is designed in Intrinsic Safety type of protection, protection level 

ia

 according to  EN 60079-11.

The marking refering to ATEX is: II 2G  Ex ia IIC T6...T1 Gb

II 2G  Ex ia IIC T6...T1 Gb

II 2G  Ex ia IIC T6...T1 Gb

II 2G  Ex ia IIC T6...T1 Gb

The marking refering to IECEx is: Ex ia IIC T6

Ex ia IIC T6

Ex ia IIC T6

Ex ia IIC T6

WARNING!

Operation with flammable products is only permitted as long as no explosive fuel/air mixture 
builds up on the inside of the flowmeter under operating conditions. The operator is responsible 
to ensure that the flowmeter is operated safely in terms of the temperature and pressure of the 
products used. In case of operation with flammable products the measuring units must be 
included in the periodic pressure tests of the system. When using the device version H250/C... 
(PTFE-liner, nonconductive) the min. conductivity of the medium must be 10

-8

 S/m, in order to 

avoid the electrostatic charge.

The marking contains the following information:

The marking contains the following information:

The marking contains the following information:

The marking contains the following information:

II

IIII

II

Explosion protection Group II

2222

Device category 2

G

G

G

G

Gas explosion protection

ia

ia

ia

ia

Intrinsic Safety type, protection level 

ia

 

IIC

IIC

IIC

IIC

suitable for gas group IIC, IIB and IIA 

T6...T1

T6...T1

T6...T1

T6...T1

suitable for temperature class T6 ... T1

Gb

Gb

Gb

Gb

EPL, suitable for zone 1

Summary of Contents for DK32 Series

Page 1: ...ical built ins Equipment category II 2 G DK32 DK34 DK32 DK34 DK32 DK34 DK32 DK34 Supplementary instructions Supplementary instructions Supplementary instructions Supplementary instructions KROHNE 04 2015 4000422303 AD DK32 34 II2G R03 en ...

Page 2: ... 1 Device description 4 2 2 Description code 4 2 3 Marking 4 2 4 Flammable products 5 2 5 Equipment category 5 2 6 Types of protection 5 2 7 Ambient temperature temperature classes 6 2 8 Electrical data 7 3 Installation 8 3 1 Installation 8 4 Electrical connections 9 4 1 General notes 9 4 2 Earthing and equipotential bonding 10 5 Operation 11 5 1 Start up 11 5 2 Operation 11 6 Service 12 6 1 Maint...

Page 3: ... with gas The EC Type Examination Certificate of the Physikalisch Technische Bundesanstalt PTB forms the basis of the EC Declaration of Conformity If required the EC Type Test Certificate can be downloaded under www krohne com 1 3 Approval according to the IECEx scheme Conformity with IECEx standards was tested in accordance with the IECEx Certification Scheme for Explosive Atmospheres as per IEC ...

Page 4: ...lized visibly with the rating plate shown below The interior of the display has an additional marking with the serial number P A 1 32 with valve and horizontal connection 34 without valve and vertical connection 2 RE inlet pressure regulator RA outlet pressure regulator 3 K1 one limit switch K2 two limit switches 4 S plug connector L cable gland incl cable 5 HT high temperature version 6 A Limit s...

Page 5: ...ding to EN 60079 11 The marking refering to ATEX is II 2G Ex ia IIC T6 T1 Gb II 2G Ex ia IIC T6 T1 Gb II 2G Ex ia IIC T6 T1 Gb II 2G Ex ia IIC T6 T1 Gb The marking refering to IECEx is Ex ia IIC T6 Ex ia IIC T6 Ex ia IIC T6 Ex ia IIC T6 WARNING Operation with flammable products is only permitted as long as no explosive fuel air mixture builds up on the inside of the flowmeter under operating condi...

Page 6: ...ditions The measuring device is installed and operated in accordance with the installation instructions in the installation and operating manual It must be ensured that the flowmeter is not heated by the effects of additional heat radiation sunshine neighbouring system components and thus operated above the permissible ambient temperature range Insulation must be limited to the piping Unobstructed...

Page 7: ... may only be connected to intrinsically safe circuits Depending on the instrument design the following maximum values apply per circuit Design DK3 A Ex Irrespective of the instrument design the following values are to be observed for each intrinsically safe circuit in case of interconnection Ui 16 VDC Ii 25 mA Pi 64 mW Ci 150 nF Li 150 µH ...

Page 8: ...observed Variable area flowmeters must be installed in such a way that There is no danger from mechanical impact effects There are no external forces affecting the indicator part The device is accessible for any visual inspections that are necessary and can be viewed from all sides The nameplate is clearly visible It can be operated from a location with secure footing CAUTION The manufacturer is n...

Page 9: ... sealing range of the cable entry The connecting cables must be fixed and laid in such a way as to be sufficiently protected against damage All cores that are not used must be securely connected to the earth potential of the hazardous area or carefully insulated against each other and against earth test voltage 500 Veff Cable entries Blanking plugs The DK3 S A Ex variable area flowmeter is equippe...

Page 10: ...ufficiently electrostatically grounded via the process cables an additional earth connection must be established using the earth screw 1 The position of the ground terminal is illustrated below The connection guarantees only an electrostatic connection of the device and does not comply with the requirements of an equipotential bonding connection DK32 DK34 ...

Page 11: ...ked for the proper state with regard to its installation and connection requirements The user of the system must have it checked before start up in compliance with the national regulations for checks before startup 5 2 Operation Setting of the limit switches may be carried out during operation Remove the housing cover to this purpose The housing cover has to be closed immediately after the limit s...

Page 12: ...e display part Due to the modular design of the variable area flowmeter it is possible to replace a complete display with an identical spare part in accordance with safety guidelines Exchanging the entire device Removal and installation is the user s responsibility Any replacement and removal should take place in a de energized state if possible If that is not possible the basic conditions for int...

Page 13: ...NOTES 7 13 DK32 DK34 www krohne com 04 2015 4000422303 AD DK32 34 II2G R03 en ...

Page 14: ...7 NOTES 14 DK32 DK34 www krohne com 04 2015 4000422303 AD DK32 34 II2G R03 en ...

Page 15: ...NOTES 7 15 DK32 DK34 www krohne com 04 2015 4000422303 AD DK32 34 II2G R03 en ...

Page 16: ... Analysis products Products and systems for the oil gas industry Measuring systems for the marine industry Head Office KROHNE Messtechnik GmbH Ludwig Krohne Str 5 47058 Duisburg Germany Tel 49 203 301 0 Fax 49 203 301 103 89 info krohne com KROHNE 04 2015 4000422303 AD DK32 34 II2G R03 en Subject to change without notice The current list of all KROHNE contacts and addresses can be found at www kro...

Reviews: