.52+1(
BM 70 A Kurzanleitung
Seite: 10
4. Entwurf 03/97
Configuration menu (Version 3.00)
Function (Fct.)
Input range
Description
1.0
OPERATION
1.1
DISPLAY
1.1.1 FCT.DISP
identical with 3.2.1
1.1.2 UNIT.LENGTH
identical with 3.2.2
1.1.3 UNIT.CONV.
identical with 3.2.3
2.0
TEST
2.1
HARDWARE
2.1.1 MASTER
Master hardware test.
2.1.2 DISPLAY
Display hardware test.
2.1.3 STATUS
Status information for Service
2.2
CUR.OUTP.I
2.2.1 VALUE I
Value display
Display of actual value of the current
output.
2.2.2 TEST I
Select
2 mA/4 mA/6 mA/...
... 20 mA/22 mA
Output of selected value to the current
output. With safety query.
2.3
SW.OUTP.
2.3.1 TEST S
Select
OPEN/CLOSE
Switch switching contact on/off.
With safety query.
2.4
FIRMWARE
2.4.1 MASTER
Display
Display of master firmware version.
2.4.2 DISPLAY
Display
Display of display firmware version.
3.0
INSTALL.
3.1
BASIC.PARAM
3.1.1 TANKHEIGHT
Select unit
m/cm/mm/
inch/Ft
Enter
0.00 [m] ... max. tank height
Enter tank height (see explanatory
notes).
The unit entered here is also used for
all other length entries.
3.1.2 BLOCKDIST
Enter
0.10 [m] ... tank height
Enter block distance = non-measurable
range below bottom edge of flange
(see explanatory notes).
3.1.3 ANTENNA
Select
STANDARD
WAVE-STICK
Select antenna type.
3.1.4 ANT.EXT.
Enter
0.00 [m] ... tank height
Enter length of antenna extension.
3.1.5 DIST.PCE.
Enter
0 ... 2000 [mm]
Enter length of distance piece above
flange.
3.1.6 STILLWELL
Select
NO / YES
If “YES“: enter
25 ... 200 [mm]
Selection: without or with still well.
With still well: enter inside diameter in
[mm].
3.1.7 REF.OFFSET
Enter
-10.00...0...+10.00 [m]
Reference offset (special function).
3.1.8 TKB.OFFSET
Enter
-100.00...0...+100.00 [m]
Tank bottom offset (special function).
3.2
DISPLAY
3.2.1 FCT.DISPLAY
Select
LEVEL
DISTANCE
CONVERSION
REFLECTION
Select function of display
(value to be displayed).
3.2.2 UNIT.LENGTH
Select
m/cm/mm/
inch/Ft/
PERCENT/BARGRAPH
Select unit for length value to be
displayed (only for level and distance).
3.2.3 UNIT.CONV.
Select
m3/l(Liter)/US Gal/
GB Gal/Ft3/bbl/PERCENT/
BARGRAPH/USER UNIT
Select unit for conversion value to be
displayed (“volume table“).
(see explanatory notes)
3.2.4 USER UNIT
Text entry
10 characters
Enter user-defined unit for the
conversion table.
3.2.5 ERROR MSG.
Select
NO/YES
Select whether error messages to be
shown in display..
3.3
SIG.OUTP.
3.3.1 FUNCTION I
Select
OFF/LEVEL/
Select function of the current output.