4. Entwurf 03/97
4. Setting the parameters
Local display
Function of keys
Operator control via the keys: For reasons of electrical safety, the keys (below the
display, when housing is open) may only be actuated for servicing and repair work
by specialist personnel, on no account, however, when there is risk of explosion!
Operator control can be carried out with the aid of the supplied bar magnet without
opening the housing. However, a particularly convenient form of parameter setting is
offered by the PC program PC-CAT (special accessories), which allows input via
masks at the computer: see PC-CAT user manual.
(cursor key):
- selects the configuration menu,
- branches the menu to the next lower level,
- shifts the cursor* to the next column on the right.
(select key):
- branches the menu to the next digit on the same level,
- changes the content (digit, text character) at the cursor*
position.
(ENTER key):
- branches the menu to the next higher level,
- stores newly entered parameters,
- executes displayed functions,
- selects special functions (e.g. error memory, see Sect. 5).
* The cursor position is signalled by flashing of the character or the option at the appropriate place.
Description of functions
The table on the following 2 pages provides an overview of all parameters that can
be set in the configuration menu.
This is followed by more precise explanations of some functions and a typical
configuration.
Numeric display, measured values
ó
Alphanumeric display, function/unit
ì
6 Markers to display measurement
status
ö
3 keys for configuration and error
interrogation
ú
Magnetic sensors for operator control
through the closed housing (function
same as the 3 keys)
÷
Compass field, indicates actuation of a
key