Rough Framing–Rough-in Vent Termination
SECTION 3
FRAMING
#CAR-39
R.11 February 2022
18
HUSSONG MFG. CO., INC.
KOZY HEAT FIREPLACES
3.6.2.4 Wall Pass Through Information and Framing
1. Measure from floor level of the fireplace to the center of where
the vent pipe will penetrate the wall. The dimensions in
are used with a Simpson DuraVent elbow.
2. Cut and frame an opening in the wall to allow the vent system to
run level through the wall pass-through.
3. Follow the vent pipe manufacturer’s installation instructions for
natural draft vent installation.
•
reflect Simpson
Duravent 5” x 8” coaxial pipe. Other manufacturers product
dimensions may vary.
•
Flexible pipe framing dimensions in
reflect Kozy
Heat #800 Series Flexible Vent System.
22”
(559mm)
1”
(25mm)
46
¼
”
(1175mm)
52
¼
”
(1327mm)
1”
(25mm)
22”
(559mm)
1”
(25mm)
1”
(25mm)
52
¼
”
(1327mm)
22”
(559mm)
1”
(25mm)
1”
(25mm)
Minimum horizontal
termination - Natural Gas
Minimum horizontal
termination -Propane
Minimum horizontal #800-1 venting
Natural gas and propane
#800-WPT3* Framing Dimensions
*Ships with #800-1 Kit
11”
(279mm)
11”
(279mm)
5
7⁄16
”
(139mm)
FIGURE 3.6
Rough-in Vent Termination Framing Dimensions
Nominal 2“ x 4” framing used in enclosure framing