Maintenance
Regularly clean the surface of the evaporator from leaves, dust and others. Switch off the
device before cleaning. In order to disable the device, select the Stand-by mode with the
knob and disconnect electric power supply. The evaporator fins are made of aluminium
strips. Do not use hard objects or detergents to clean the evaporator fins containing
chlorine, acids or abrasives; use generally available preparations for cleaning evaporators
and condensers in air-conditioning and cooling installations. After cleaning, check the
condensate drain. While plentiful snowfall, snow can accumulate on the evaporator
and on the top cover of the heat pump. Snow must be cleared to avoid ice formation.
Necessary steps including zero commissioning are:
1. Start-up of the HP heating system and checking its operation (proper setting of
operating parameters and matching them to the properties of the thermal insulation
of the building, installation).
2. Configuration and setting of basic operating parameters (programming room
temperature and DHW).
3. Assessment of the assembly in terms of leaks, disturbing noises (e.g. noise at poor
deaeration).
4. Initial user instruction in the use of the HP system
5. Record the relevant parameters in the Start-up chart form in the HPM.Z operating
instruction.
6. Zero Commissioning registration by the installation company in the Aura Kospel
system, https://aura.kospel.pl/commission/createFromShortcut? shortcut_id = 27.