Technical data
Instruction for the installer
Boiler installation
Installation conditions
• an appropriate power supply,
• an efficient electrical installation which has been completed in accordance with the binding norms of electric installation,
• wet central heating system equipped with an appropriate expansion vessel made according to the binding norms of hydraulic
installation,
• the heating installation needs to be flushed thoroughly before the installation,
• the boiler must be protected from dirt by using a magnetic filter,
• do not install any barrier fittings (e.g. valves) on the outlet of the safety valve,
• this appliance must not be installed in a humid place or in a place exposed to the danger of explosion,
• if the boiler is to co-operate with an under-floor heating system protecting fittings must be installed (fig. 2b or 3).
A magnetic filter must be installed on return pipe of central heating installation system (before
boiler inlet). The filter must be installed in horizontal position, accordingly to flow direction (see
arrow on the filter body), with the magnetic insert chamber to the bottom.
Maximal pressure
MPa
0,3
Minimal pressure
MPa
0,05
Outflow water temperature
°C
20 ÷ 85
Max. water temperature
°C
100
Dimensions (height x width
x depth)
EKCO.M1z
mm
660 x 380 x 175
EKCO.M1Nz
700 x 425 x 285
EKCO.TM
815 x 503 x 197
Weight
EKCO.M1z
kg
~16
EKCO.M1Nz
24,5
EKCO.TM
~29
Water connections
EKCO.M1z, EKCO.M1Nz
G 3/4”
EKCO.TM
G 1”
Safety class
IP 21
Boiler type
EKCO.M1z, EKCO.M1Nz
Rated power
kW
4
6
8
12
4
6
8
12
Rated voltage
220V~
380V 3N~
Rated current
A
18,0
27,27
36,5
54,5
3 x 6,1
3 x 9,1 3 x 12,8 3 x 18,3
Fuse rated current
A
25
32
40
63
10
16
25
Minimal connecting wires diameter
mm
2
3 x 2,5
3 x 4
3 x 6
3 X 10
5 x 1,5
5 x 2,5
The maximum allowed network impedance
Ω
0,44
0,39
0,34
Boiler type
EKCO.M1z, EKCO.M1Nz
EKCO.TM
Rated power
kW
15
18
21
24
30
36
42
48
Rated voltage
380V 3N~
Rated current
A
3 x 22,8 3 x 27,4 3 x 31,9 3 x 36,5 3 x 45,6 3 x 54,5 3 x 63,9 3 x 73,0
Fuse rated current
A
25
32
40
50
63
80
100
Minimal connecting wires diameter
mm
2
5 x 2,5
5 x 4
5 x 6
5 x 10
5 x 16
Maximal connecting wires
diameter
EKCO.M1z, EKCO.M1Nz
mm
2
5 x 16
EKCO.TM
phase conductor (2 x 16 each), neutral and protective conductor (1x16)
The maximum allowed network impedance
Ω
0,14
0,09
0,035
0,03