![Koso REXA Electraulic Xpac Installation And Operation Manual Download Page 84](http://html1.mh-extra.com/html/koso/rexa-electraulic-xpac/rexa-electraulic-xpac_installation-and-operation-manual_1999189084.webp)
Xpac
Installation Manual -- Version 5.1 (5/09)
C-10
REXA
Electraulic Actuators & Drives
C.6.1 0.05% Deadband
The 0.05% deadband option will double the standard precision and
provide resolution within one half the thickness of a piece of paper
on a 2 inch rated stroke. The control of an Xpac actuator with this
setting is remarkable. The positioning is smooth and continuous
without resolution hop. Deadband (db) is set in the normal manner
per Section 6.3.1. The minimum allowable setting is now 0.05%.
There are two potential problems, noise and oscillation, involved in
such installations. Noise on the control and feedback signals may
be interpreted as real values. Isolated signal lines, shielded cables
and proper grounding are typical requirements for fine control.
Actuator oscillation around the control point will more easily occur
at low deadband settings. The acceleration of the actuator can be
adjusted to prevent continuous overshoot of position. A low accel-
eration rate can be set for a small change in control signal, while a
much higher rate may be set for larger changes (see section 6.3.2).
C.6.2 Minimum Control Point
Most specialized anti-cavitation or low noise valves reduce the fluid
energy by staged pressure reduction within a labyrinth cage. These
designs are only effective if there is sufficient fluid flow through
the resistive element. At plug lifts below a minimum control point,
pressure reduction will occur between the plug and seat ring which
may damage the valve.
The Minimum Control Point feature allows the setting of a point
below which the actuator will not modulate. Any control signal that
specifies a position below the minimum control point will result in
the actuator moving to the fully closed position. Normal operation
of the actuator will occur for control signals specifying a position
above this point.
CPt - CONTROL POINT SUB-MENU
Before establishing a minimum control point, the stroke of the ac-
tuator must be set by entering Position Low (PL) and Position High
(PH) in the Cal Sub-Menu.
Step over to the CPt Sub-Menu, and then step down to the Con-
trol Point parameter, CP. Using the Scroll Up/ Scroll Down keys,
position the actuator to the desired point and press (E)NTER. The
displayed value is the Minimum Control Point in percent of stroke.
For linear operation ([FCH:FC] = OFF), the control signal corre-
sponding to this point is the sum of the value of Signal Low and
If the value of PL or PH is changed,
the minimum control point must be
reset.
CONTROL POINT
Summary of Contents for REXA Electraulic Xpac
Page 1: ...IOM 05 09...
Page 2: ...Xpac Installation Manual Version 5 1 5 08 REXA Electraulic Actuators Drives 2...
Page 8: ......
Page 60: ......
Page 61: ...A 3...
Page 62: ...A 4...
Page 63: ...A 5...
Page 64: ...A 6...
Page 65: ...A 7...
Page 66: ...A 8...
Page 67: ...A 9...
Page 68: ...A 10...
Page 69: ...A 11...
Page 70: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 76: ......
Page 87: ...REXA Electraulic Actuators Drives Xpac Installation Manual Version 5 1 5 09 C 13 Figure C A...
Page 88: ......
Page 90: ......
Page 96: ......
Page 100: ......
Page 104: ......
Page 114: ......
Page 124: ......
Page 128: ......
Page 130: ......
Page 136: ......
Page 138: ......
Page 142: ......
Page 146: ......
Page 155: ...X 11...
Page 156: ...X 12...
Page 157: ...X 13...
Page 158: ...X 14...
Page 159: ...X 15...
Page 160: ...X 16...
Page 161: ...X 17...
Page 162: ...X 18...
Page 163: ...X 19...
Page 164: ......