![Koralewski EasyRange FS-21 Manual Download Page 12](http://html1.mh-extra.com/html/koralewski/easyrange-fs-21/easyrange-fs-21_manual_1997676012.webp)
12/27
F i l t e r C o n t r o l F S - 2 1
FS-21.doc | Status 2015 - 02 - 09
4.3.2
Setting the Regeneration Time
Time and day(s) are entered here, at which regeneration is to be accomplished.
Note
: Scroll through the different setting points of the sub-menu Regeneration Times with
UP/DOWN. (
see also chap. 4.3.11.1 Filter capacity
setting option: Time
/
selection weekdays: yes
or
no
4.3.3
External - / Quality dependent Regeneration Release
If this type of release is selected, regeneration will be released by an external signal, which
is connected e.g. to E2 (Kl25). This external signal may come from a water analysis device
( residual hardness analyser ) or from a control room.
selection: yes
or
no
4.3.4
External - / Quality dependent Regeneration Release (delayed)
If the filter shall be regenerated via an external signal, however at a certain time only,
regeneration release will be set to time and externally.
selection: yes
or
no
4.3.5
Regeneration Release according to Quantity
If the filter should only be regenerated according to the predetermined and appropriately
configured filter capacity (
ref. to chap. 4.3.11 Setting the Regeneration Quantities
), the
regeneration release is set to Quantity in the FS-21 configuration.
selection: yes
or
no
Note: If a new regeneration amount was entered, the new regeneration amount will
be effective after the regeneration of both filter with the old amount.
4.3.6
Regeneration Release according to Quantity (delayed)
If the filter should be regenerated according to a specific quantity of water (
ref. to chap.
4.3.11 Setting the Regeneration Quantities
), but also at a specific time, the regeneration
release is set to Quantity and Time in the FS-21 configuration.
selection: yes
or
no
Regeneration Times
Time
12:00
Regeneration Times
Reg. on Monday
Yes
Regeneration times
Reg. on Tuesday
No
Regeneration times
Reg. on Wednesday
Yes
Time dept. Reg.
Yes
Quantity Reg.
Yes
4
Quantity Reg.
Yes
Quality Reg.
Yes
Time dept. Reg.
Yes
Quality Reg.
Yes