Electrical Control Function
Electrical Control System
97
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temp.(heating T2
,
cooling T2B)
If the temp. is lower than -9 degree, the digital display tube will
show “-9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected,
the digital display tube will show: “
――
”
07
Condenser pipe temp.(T3)
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
The display value is between 0~129 degree.If the temp. is
higher than 99 degree, the digital display tube will show single
digit and tens digit. (For example, the digital display tube show
“0.5”,it means the compressor discharge temp. is 105 degree.
the digital display tube show “1.6”,it means the compressor
discharge temp. is 116 degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4,
Dry:6,Self-clean:8, Forced defrosting:10
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4,
Dry:6,Self-clean:8, Forced defrosting:10
14 EXV
open
angle
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
For example ,the digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
15 Frequency
limit
symbol
Bit7
Frequency limit
caused by IGBT
radiator
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.
Bit6
Frequency limit
caused by PFC
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by T5.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
16
DC fan motor speed
0
:
Off 1 Turbo 2 High 3 Medium 4.Low 5 Breeze 6
Supper breeze
17
IGBT radiator temp.
The display value is between 0~130 degree..If the temp. is
higher than 99 degree, the digital display tube will show single
digit and tens digit. (For example, the digital display tube show
“0.5”,it means the IGBT radiator temp. is 105 degree. the
digital display tube show “1.6”,it means the IGBT radiator
temp. is 116 degree)
18
Indoor unit number
The indoor unit can communicate with outdoor unit well.
General:1, Twins:2
19
Condenser pipe temp. of 1# indoor unit
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the capacity demand is 0, , the
digital display tube will show “0. If the indoor unit is not
connected, the digital display tube will show: “
――
”(heating
T2
,
cooling T2B)
20
Condenser pipe temp. of 2# indoor unit
21 Reserved
22
1# Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0). If the indoor unit is not connected, the digital
display tube will show: “
――
”
23
2# Indoor unit capacity demand code
24 Reserved
Summary of Contents for KV24 ODU-ARF21C
Page 1: ......
Page 6: ...Nomenclature 4 General Information 3 Nomenclature 3 1 Indoor Outdoor Unit...
Page 11: ...Features Indoor Units 9 Alarm lamp Long distance on off controller...
Page 13: ...Service Space Indoor Units 11 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 19: ...Field Wiring Indoor Units 17 9 Field Wiring 24K 36K...
Page 20: ...Field Wiring 18 Indoor Units 48K 60K...
Page 34: ...Field Wiring 32 Indoor Units 10 Field Wiring 24K 36K...
Page 35: ...Field Wiring Indoor Units 33 48K 60K...
Page 39: ...Service Space Indoor Units 37 3 Service Space...
Page 44: ...Ceiling Floor Type 42 Ceiling Floor Type 9 Field Wiring 24K 36K...
Page 45: ...Ceiling Floor Type Ceiling Floor Type 43 48K 60K...
Page 49: ...Service Space Floor standing Type 47 3 Service Space...
Page 50: ...Wiring Diagrams 48 Floor standing Type 4 Wiring Diagrams KV36FM ARF21C KV60FM ARF21C...
Page 55: ...Field Wiring Floor standing Type 53 9 Field Wiring 36K...
Page 56: ...Field Wiring 54 Floor standing Type 60K...
Page 59: ...Dimensions Outdoor Units 57 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 62: ...Wiring Diagrams 60 Outdoor Units 4 Wiring Diagrams KV24ODU ARF21C KV36ODU ARF21C...
Page 63: ...Wiring Diagrams Outdoor Units 61 KV48ODU ARF21C KV60ODU CRF21C...
Page 103: ...Troubleshooting Electrical Control System 101 2 1 5 Display board of floor standing...
Page 113: ...Troubleshooting Electrical Control System 111 2 4 4 2 E1 malfunction For 485 communication E1...
Page 114: ...Troubleshooting 112 Electrical Control System 2 4 4 3 J4 malfunction J4...
Page 116: ...Troubleshooting 114 Electrical Control System 2 4 4 5 P6 malfunction P6...
Page 117: ...Troubleshooting Electrical Control System 115 2 4 4 6 J5 malfunction J5...
Page 119: ...Troubleshooting Electrical Control System 117 2 4 4 8 F0 malfunction F0...
Page 123: ...Troubleshooting Electrical Control System 121 2 4 4 12 J0 malfunction J0...