6. Drainage pipe installation
Installation
83
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers.
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Summary of Contents for KV24 ODU-ARF21C
Page 1: ......
Page 6: ...Nomenclature 4 General Information 3 Nomenclature 3 1 Indoor Outdoor Unit...
Page 11: ...Features Indoor Units 9 Alarm lamp Long distance on off controller...
Page 13: ...Service Space Indoor Units 11 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 19: ...Field Wiring Indoor Units 17 9 Field Wiring 24K 36K...
Page 20: ...Field Wiring 18 Indoor Units 48K 60K...
Page 34: ...Field Wiring 32 Indoor Units 10 Field Wiring 24K 36K...
Page 35: ...Field Wiring Indoor Units 33 48K 60K...
Page 39: ...Service Space Indoor Units 37 3 Service Space...
Page 44: ...Ceiling Floor Type 42 Ceiling Floor Type 9 Field Wiring 24K 36K...
Page 45: ...Ceiling Floor Type Ceiling Floor Type 43 48K 60K...
Page 49: ...Service Space Floor standing Type 47 3 Service Space...
Page 50: ...Wiring Diagrams 48 Floor standing Type 4 Wiring Diagrams KV36FM ARF21C KV60FM ARF21C...
Page 55: ...Field Wiring Floor standing Type 53 9 Field Wiring 36K...
Page 56: ...Field Wiring 54 Floor standing Type 60K...
Page 59: ...Dimensions Outdoor Units 57 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 62: ...Wiring Diagrams 60 Outdoor Units 4 Wiring Diagrams KV24ODU ARF21C KV36ODU ARF21C...
Page 63: ...Wiring Diagrams Outdoor Units 61 KV48ODU ARF21C KV60ODU CRF21C...
Page 103: ...Troubleshooting Electrical Control System 101 2 1 5 Display board of floor standing...
Page 113: ...Troubleshooting Electrical Control System 111 2 4 4 2 E1 malfunction For 485 communication E1...
Page 114: ...Troubleshooting 112 Electrical Control System 2 4 4 3 J4 malfunction J4...
Page 116: ...Troubleshooting 114 Electrical Control System 2 4 4 5 P6 malfunction P6...
Page 117: ...Troubleshooting Electrical Control System 115 2 4 4 6 J5 malfunction J5...
Page 119: ...Troubleshooting Electrical Control System 117 2 4 4 8 F0 malfunction F0...
Page 123: ...Troubleshooting Electrical Control System 121 2 4 4 12 J0 malfunction J0...