6. Drainage pipe installation
Installation
85
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
shall cause shutdown of unit. When this situation happens, the normal startup only can be recovered by
turning down power supply and eliminating accumulated water.
Note:
Drain plug at the main water-containing plate is used for eliminating accumulated water in
water-containing plate when maintaining air conditioner fault. During normal operation, the plug shall be
filled in to prevent leakage.
6.4 Insulation work of drainage pipe
Refer the introduction to the insulation engineering parts.
Summary of Contents for KV24 ODU-ARF21C
Page 1: ......
Page 6: ...Nomenclature 4 General Information 3 Nomenclature 3 1 Indoor Outdoor Unit...
Page 11: ...Features Indoor Units 9 Alarm lamp Long distance on off controller...
Page 13: ...Service Space Indoor Units 11 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 19: ...Field Wiring Indoor Units 17 9 Field Wiring 24K 36K...
Page 20: ...Field Wiring 18 Indoor Units 48K 60K...
Page 34: ...Field Wiring 32 Indoor Units 10 Field Wiring 24K 36K...
Page 35: ...Field Wiring Indoor Units 33 48K 60K...
Page 39: ...Service Space Indoor Units 37 3 Service Space...
Page 44: ...Ceiling Floor Type 42 Ceiling Floor Type 9 Field Wiring 24K 36K...
Page 45: ...Ceiling Floor Type Ceiling Floor Type 43 48K 60K...
Page 49: ...Service Space Floor standing Type 47 3 Service Space...
Page 50: ...Wiring Diagrams 48 Floor standing Type 4 Wiring Diagrams KV36FM ARF21C KV60FM ARF21C...
Page 55: ...Field Wiring Floor standing Type 53 9 Field Wiring 36K...
Page 56: ...Field Wiring 54 Floor standing Type 60K...
Page 59: ...Dimensions Outdoor Units 57 Model KBtu h Unit mm W D H W1 A B 48 60 952 415 1333 1045 634 404...
Page 62: ...Wiring Diagrams 60 Outdoor Units 4 Wiring Diagrams KV24ODU ARF21C KV36ODU ARF21C...
Page 63: ...Wiring Diagrams Outdoor Units 61 KV48ODU ARF21C KV60ODU CRF21C...
Page 103: ...Troubleshooting Electrical Control System 101 2 1 5 Display board of floor standing...
Page 113: ...Troubleshooting Electrical Control System 111 2 4 4 2 E1 malfunction For 485 communication E1...
Page 114: ...Troubleshooting 112 Electrical Control System 2 4 4 3 J4 malfunction J4...
Page 116: ...Troubleshooting 114 Electrical Control System 2 4 4 5 P6 malfunction P6...
Page 117: ...Troubleshooting Electrical Control System 115 2 4 4 6 J5 malfunction J5...
Page 119: ...Troubleshooting Electrical Control System 117 2 4 4 8 F0 malfunction F0...
Page 123: ...Troubleshooting Electrical Control System 121 2 4 4 12 J0 malfunction J0...