Drainage pipe installation
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers.
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
95
Summary of Contents for KV 24CC-ARF21
Page 1: ......
Page 5: ...3...
Page 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Page 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Page 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Page 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Page 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Page 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Page 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Page 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Page 36: ...34...
Page 38: ...Service Space 3 Service Space 36...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Page 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Page 48: ...46...
Page 50: ...Service Space 3 Service Space 48...
Page 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Page 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Page 56: ...54...
Page 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Page 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Page 62: ...Accessories 7 Accessories 60...
Page 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Page 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Page 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Page 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Page 73: ...Wiring Diagrams KV60ODU CRF21 71...
Page 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Page 118: ...2 4 1 2 Outdoor unit malfunction 116...
Page 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Page 122: ...2 4 2 3 E3 malfunction 120...
Page 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Page 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Page 128: ...2 4 2 9 P3 malfunction 126...
Page 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...