Engineering of electrical wiring
9.2.3 Insulation material selection for drainage pipe
The insulation material should be flame retardant material, the flame retardancy of the material should
be selected according to the local law.
Thickness of insulation layer is usually above 10mm.
Use specific glue to paste the seam of insulation material, and then bind with adhesive tape. The width
of tape shall not be less than 5cm. Make sure it is firm
to
avoid dew.
9.2.4 Installation and highlights of insulation construction
The single pipe should be insulated before connecting to another pipe, the joint part should be insulated
after the drainage test.
There should be no insulation gap between the insulation material.
10. Engineering of electrical wiring
10.1 Highlights of electrical wiring installation
All field wiring construction should be finished by qualified electrician.
Air conditioning equipment should be grounded according to the local electrical regulations.
Current leakage protection switch should be installed.
Do not connect the power wire to the terminal of signal wire.
When power wire is parallel with signal wire, put wires to
separate
wire tube and remain at least 300mm
gap.
Select wiring a
ccording to table in indoor part named “the specification of power” , make sure
the selected wiring
is
not small
er
than the dat
a
show
n
in the table.
Select different colors for different wire according to relevant regulations.
Do not use metal wire tube at the place with acid or alkali corrosion, adopt plastic wire tube to replace it.
There must
not be
wire connect joint in the wire tube
,
If joint is a must, set a connection box at the place.
The wiring with different voltage should not be in one wire tube.
Ensure that the color of the wires of outdoor and the terminal No. are same as those of indoor unit
respectively.
101
Summary of Contents for KV 24CC-ARF21
Page 1: ......
Page 5: ...3...
Page 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Page 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Page 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Page 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Page 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Page 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Page 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Page 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Page 36: ...34...
Page 38: ...Service Space 3 Service Space 36...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Page 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Page 48: ...46...
Page 50: ...Service Space 3 Service Space 48...
Page 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Page 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Page 56: ...54...
Page 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Page 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Page 62: ...Accessories 7 Accessories 60...
Page 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Page 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Page 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Page 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Page 73: ...Wiring Diagrams KV60ODU CRF21 71...
Page 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Page 118: ...2 4 1 2 Outdoor unit malfunction 116...
Page 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Page 122: ...2 4 2 3 E3 malfunction 120...
Page 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Page 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Page 128: ...2 4 2 9 P3 malfunction 126...
Page 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...