Electrical Control Function
When T4 <15
℃
and T3 < 30
℃
, the unit will enter into low ambient cooling mode. The outdoor fan will
choose speed according to T3.
When T3
≥
38
℃
or when T4
≥
20
℃
, the outdoor fan will choose the speed according to T4 again.
1.3.2.3 Indoor fan
operation
rules
In cooling mode, indoor fan runs all the time and the speed can be selected as high, (medium), low and auto.
The auto fan:
5.0
4.0
High
Low
2.0
Medium
3.0
1.3.2.4 Evaporator low temperature T2 protection.
When T2<2
℃
and lasts for 3 minutes, the indoor has no capacity demand and resume till T2
≥
7
℃
.
1.3.2.5 Condenser high temperature T3 protection
When T3>65
℃
for 3 seconds, the compressor will shut off. When T3
<
52,the compressor will restart.
1.3.3 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
∆
T (
∆
T =T1-Ts).
∆
T=T1-Ts Running
mode
∆
T
≥
2
℃
Cooling
∆
T<2
℃
Fan-only
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.
1.3.5 Drying mode
Drying mode works the same as cooling mode in low speed.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
106
Summary of Contents for KV 24CC-ARF21
Page 1: ......
Page 5: ...3...
Page 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Page 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Page 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Page 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Page 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Page 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Page 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Page 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Page 36: ...34...
Page 38: ...Service Space 3 Service Space 36...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Page 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Page 48: ...46...
Page 50: ...Service Space 3 Service Space 48...
Page 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Page 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Page 56: ...54...
Page 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Page 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Page 62: ...Accessories 7 Accessories 60...
Page 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Page 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Page 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Page 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Page 73: ...Wiring Diagrams KV60ODU CRF21 71...
Page 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Page 118: ...2 4 1 2 Outdoor unit malfunction 116...
Page 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Page 122: ...2 4 2 3 E3 malfunction 120...
Page 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Page 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Page 128: ...2 4 2 9 P3 malfunction 126...
Page 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...