![koppel KV 24CC-ARF21 Service Manual Download Page 110](http://html1.mh-extra.com/html/koppel/kv-24cc-arf21/kv-24cc-arf21_service-manual_1997603110.webp)
Electrical Control Function
Press the switch N times it will display the content corresponding to No. N. After getting into the check
function, it will display No. N with 1.5s, meanwhile the low bit decimal of digit display flashing, indicated to
get into the check function display. After 1.5s, it will display the content corresponding to No. N.
the digital display tube will display the follow
ing
when push SW1 each time.
N Display
Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator temp.(T2)
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube will
show “-9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected,
the digital display tube will show: “
――
”
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(Tp)
The display value is between 13~120 degree. If the temp. is
lower than 13 degree, the digital display tube will show “13”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show “0.5”,it means the compressor discharge
temp. is 105 degree. the digital display tube show “1.6”,it
means the compressor discharge temp. is 116 degree)
For
KV48ODU-ARF21B
&
KV60ODU-CRF21
The
display
value
is between 13~129 degree. If the temp. is
lower
than 13
degree, the digital display tube will show “13”.
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
For
KV48ODU-ARF21B & KV60ODU-CRF21
, Off:0, Fan
only
1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14 EXV
open
angle
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
For example ,the digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
15 Frequency
limit
symbol
Bit7
Frequency limit
caused by IGBT
radiator
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.
Bit6
Frequency limit
caused by PFC
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2 Frequency
limit
108
Summary of Contents for KV 24CC-ARF21
Page 1: ......
Page 5: ...3...
Page 13: ...Dimensions 2 Dimensions Unit mm MODEL A B C H KV24CC ARF21 230 15 9 9 52 260 11...
Page 14: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000mm 12...
Page 15: ...Wiring Diagrams 4 Wiring Diagrams KV24CC ARF21 13...
Page 21: ...Field Wiring 11 Field Wiring KV24CC ARF21 19...
Page 27: ...Dimensions 2 Dimensions Capacity Btu h A H 36 245 275 48 245 275 25...
Page 28: ...Service Space 3 Service Space 1000mm 1000mm 1000mm 1000m m 26...
Page 29: ...Wiring Diagrams 4 Wiring Diagrams KV36CC ARF21B KV48CC ARF21B 27...
Page 34: ...Field Wiring 9 Field Wiring KV36CC ARF21B KV48CC ARF21B 32...
Page 36: ...34...
Page 38: ...Service Space 3 Service Space 36...
Page 39: ...Wiring Diagrams 4 Wiring Diagrams KV24CM ARF21 37...
Page 46: ...Field Wiring 11 Field Wiring KV24CM ARF21 44...
Page 48: ...46...
Page 50: ...Service Space 3 Service Space 48...
Page 51: ...Wiring Diagrams 4 Wiring Diagrams KV36CM ARF21B KV48CM ARF21B 49...
Page 54: ...Field Wiring 9 Field Wiring KV36CM ARF21B KV48CM ARF21B 52...
Page 56: ...54...
Page 58: ...Service Space 56 GA Floor standing Type 3 Service Space 56...
Page 59: ...Wiring Diagrams 4 W iring Diagrams KV36FM ARF21 KV60FM ARF21 57...
Page 62: ...Accessories 7 Accessories 60...
Page 64: ...Field Wiring 9 Field Wiring KV36FM ARF21 KV60FM ARF21 62...
Page 70: ...Wiring Diagrams 4 Wiring Diagrams KV24ODU ARF21 220075301510 KV24ODU ARF21 220075301740 68...
Page 71: ...Wiring Diagrams KV36ODU ARF21 B 220075501730 KV36ODU ARF21 B 220075502120 69...
Page 72: ...Wiring Diagrams KV48ODU ARF21B 70...
Page 73: ...Wiring Diagrams KV60ODU CRF21 71...
Page 113: ...Troubleshooting 2 1 5 Display board of Floor standing 111...
Page 118: ...2 4 1 2 Outdoor unit malfunction 116...
Page 121: ...Troubleshooting Electrical Control System 2 4 2 2 E2 malfunction 119...
Page 122: ...2 4 2 3 E3 malfunction 120...
Page 126: ...2 4 2 7 P1 malfunction Only for 36K 52K 124...
Page 127: ...Troubleshooting 2 4 2 8 P2 malfunction Only for 36K 52K 125...
Page 128: ...2 4 2 9 P3 malfunction 126...
Page 131: ...Troubleshooting 2 4 2 12 P6 malfunction For single phase units 129...