Principles of Operation (con’t) 

 

 

 

MAX AND MIN TEMPERATURE MEMORIZATION 

HOW TO SEE THE MIN TEMPERATURE: 

 

1) Press and release the down arrow       key. 

2) The “Lo” message will be displayed followed 

    by the minimum temperature recorded. 

3) Press the down arrow       key again or wait 5 seconds 

    to restore normal display. 

 

HOW TO SEE THE MAX TEMPERATURE: 

 

1) Press and release the up       arrow key. 

2) The “Hi” message will be displayed followed 

    by the maximum temperature recorded. 

3) Press the up arrow        key again or wait 5 seconds to 

    restore normal display. 

 

HOW TO RESET THE MAX AND MIN TEMPERATURE 
RECORDED: 

 

1) Press the SET key for more than 3 seconds while the 

    max or min temperature is displayed. (rSt message 
    will be displayed.) 

2) To confirm the operation, the “rSt” message starts 

    blinking and the normal temperature will be displayed. 

 

MAIN FUNCTIONS 

HOW TO SEE THE SETPOINT: 

 

1) Press and immediately release the SET key. 

    The display will show the set point value. 

2) Press and immediately release the SET key, or 

    wait 5 seconds to display the probe value again. 

 

HOW TO CHANGE THE SETPOINT: 

NOTE: The standard set point is 75°.   

 

1) Press the SET key for more than 2 seconds to 

    change the set point value. 

2) The value of the set point will be displayed and 

    the °

or

 

°

LED

 

starts blinking. 

3) To change the set value push the up        or down 

    arrow        keys within 10 seconds. 

4) To store the new set point value push the SET 

    key again, or wait 10 seconds.  

 

HOW TO CHANGE A PARAMETER VALUE: 

 

To change a parameter’s value, operate as follows: 

 

1) Enter the Programming mode by pressing the  

    SET plus down arrow keys for 3 seconds (the 
    °

or

 

°

LED

 

starts blinking). 

6

2) Select the required parameter. Press the SET 

    key to display its value.  

3) Use up or down arrow keys to change its value. 

4) Press SET to store the new value and move to 

    the following parameter. To exit, press SET and 
    the up arrow keys or wait 15 seconds without 
    pressing a key. 

    NOTE: The set value is stored even when the 
    procedure is exited by waiting for the time-out 
    to expire. 

 

HOW TO LOCK THE KEYBOARD: 

 

1) Press and hold the up and down arrow keys 

    simultaneously for more than 3 seconds.  

2) The POF message will be displayed, and the 

    keyboard will be locked. At this point, it will only 
    be possible to see the set point or the MAX or 
    MIN temperature stored.  

3) If a key is pressed more than 3 seconds, the 

    POF message will be displayed. 

 

HOW TO UNLOCK THE KEYBOARD: 

 

1) Press and hold the up and down arrow keys 

    simultaneously for more than 3 seconds until 
    the Pon message is displayed.  

 

OPTIONAL MONITORING SYSTEM 

TTL SERIAL LINE - FOR OPTIONAL MONITORING 
SYSTEMS: 

 

The optional TTL serial line, available through the 
HOT KEY connector, allows through the use of 
the external TTL/RS485 converter, connection of 
this digital converter to a monitoring system that is 
ModBUS-RTU compatable (X-WEB500/3000/300). 
Connections are provided through an external 2-
position terminal block. 

 

Summary of Contents for Intrepid Series

Page 1: ...HAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 95 12 21 CDR 20369 INTREPID SE...

Page 2: ...X Warranty 17 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes o...

Page 3: ...minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure t...

Page 4: ...the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure...

Page 5: ...oltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperatures CONTROL ACTION The evaporator blower oper...

Page 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...tor blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compressor to operate the factory setting is 7...

Page 9: ...e casters will prevent both rolling and swivelling The casters are factory set to a minimum height and provide one inch of adjustment To adjust the height loosen the two allen head set screws in the c...

Page 10: ...Drawings and Dimensions 10 DRAWINGS ATTACHED...

Page 11: ...imit 0712 32 Condensate Pump 0664 01 Standard Features Adjustable Casters Baked Powder Finish Blygold PoluAI XT Coil Coating Closed Loop Cooling Condenser Blower Controller Compressor Crankcase Heater...

Page 12: ...12 Wiring Diagram WIRING DIAGRAMS ATTACHED...

Page 13: ...13 Commissioning Test Results COMMISSIONING TEST RESULTS ATTACHED...

Page 14: ...reset thermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are...

Page 15: ...ilter and secure in position by tightening the center screw 3 Lift filter up slightly to clear lower bracket and pull away from unit 4 Place new filter in lower bracket with flow arrows pointing towar...

Page 16: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Bl...

Page 17: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: