V. Principles of Operation 

 

Kooltronic Air Conditioners are required when the equipment operating 
temperature must be kept near or lower than the ambient room temperature, 
and/or the cabinet must be sealed from dust, fumes, oil, corrosives and other 
contaminants. These Air Conditioners utilize a "Closed-Loop Cooling System" to 
ensure optimum performance of the installed components. 

 
Closed-Loop cooling seals the electronic enclosure from hostile elements in the 
environment. Two separate circulation systems are employed. The internal system 
cools and dehumidifies the air inside the cabinet, totally isolating the sensitive 
electronics and other components from the environment. The external system 
uses circulating ambient air or water to discharge the heat removed from the 
electronics. The heat is dissipated from the enclosure by means of the vapor 
compression refrigeration cycle. This takes place in a hermetically-sealed 
refrigeration system, utilizing either an air-cooled or water-cooled condenser heat 
exchanger. The warm air inside the enclosure is drawn through the evaporator coil 
where it is cooled, dehumidified and returned. 

Any enclosure moisture accumulated on the evaporator coil is collected in the 
condensate tray and removed through the drain tube.  

The heat removed through the evaporator coil is transferred by the compressed refrigerant to the condenser coil. Ambient 
air is then passed through the condenser coil, where it absorbs the heat and is then discharged to the environment. 

When the Kooltronic Air Conditioner is properly sized it should operate constantly and maintain 75°F to 115°F enclosure 
temperature, depending on the ambient temperatures. 

 

 

 

 
 

CONTROL ACTION 

The evaporator blower operates continuously. The compressor is cycled on and off by the action from the factory preset 
programmable thermostat. A pressure switch controls the on/off action of the 
condenser blower. 

The regulation is performed according to the temperature measured by the 
thermostat probe with a positive differential from the set point: if the 
temperature increases and reaches set point plus differential the compressor 
is started and then turned off when the temperature reaches the set point 
value again. 

In case of fault in the thermostat probe the start and stop of the compressor 
are timed through preset parameters. 

The programmable thermostat is located as shown in the upper right ISO 
illustration. WARNING: the programmable device is preprogrammed and set at the factory. In the event changes are needed 
the following instructions can be used.

 

FRONT PANEL COMMANDS 

FRONT PANEL LED INDICATORS

 - To display target set point; in programming mode it selects a parameter or confirms an operation.

(UP)

 - To see the max. stored temperature; in programming mode it browses the parameter codes or increases the displayed value.

(DOWN)

 - To see the min. stored temperature; in programming mode it browses the parameter codes or decreases the displayed value.

 - To switch the instrument off, if onF = oFF.

 - Not enabled.

(DEF)

 - To start a manual defrost.

KEY COMBINATIONS

To lock and unlock the keyboard.

To return to the room temperature display.

To enter programming mode.

PROGRAMMABLE 
THERMOSTAT 
(BEHIND
COVER)

COOL AIR
DISCHARGE

WARM AIR
RETURN

EP56TR-4

Summary of Contents for Intrepid Series

Page 1: ...HAT THIS MANUAL BE READ AND UNDERSTOOD THOROUGHLY KOOLTRONIC INC 30 Pennington Hopewell Road Pennington NJ 08534 609 466 3400 FAX 609 466 1114 www kooltronic com 900 039 95 12 21 CDR 20369 INTREPID SE...

Page 2: ...X Warranty 17 I Introduction Kooltronic Air Conditioners are designed to provide a cool dehumidified environment for your electronic components There are models to fit virtually all sizes and shapes o...

Page 3: ...minimum of 5 minutes prior to operating in order to allow the compressor oil to drain to the compressor sump area CAUTION 3 Before operating this unit all electrical wiring must be checked to assure t...

Page 4: ...the power source matches these requirements y Use of incorrect type or amount of refrigerant will adversely affect performance and may damage the unit r Make sure that these parameters are met Failure...

Page 5: ...oltronic Air Conditioner is properly sized it should operate constantly and maintain 75 F to 115 F enclosure temperature depending on the ambient temperatures CONTROL ACTION The evaporator blower oper...

Page 6: ...the new set point value push the SET key again or wait 10 seconds HOW TO CHANGE A PARAMETER VALUE To change a parameter s value operate as follows 1 Enter the Programming mode by pressing the SET plu...

Page 7: ...p code 7 0 65535 rEL Software release 0 rSE Real set point 0 onF on off key enabling ES PbC Kind of probe ntc Adr Serial address 1 1 247 HES Differential for energy saving 0 F 54 54 rrd Regulation res...

Page 8: ...tor blower or fan is running 5 Observe the temperature on the digital display The thermostat must be set a minimum of 10 F below this temperature for the compressor to operate the factory setting is 7...

Page 9: ...e casters will prevent both rolling and swivelling The casters are factory set to a minimum height and provide one inch of adjustment To adjust the height loosen the two allen head set screws in the c...

Page 10: ...Drawings and Dimensions 10 DRAWINGS ATTACHED...

Page 11: ...imit 0712 32 Condensate Pump 0664 01 Standard Features Adjustable Casters Baked Powder Finish Blygold PoluAI XT Coil Coating Closed Loop Cooling Condenser Blower Controller Compressor Crankcase Heater...

Page 12: ...12 Wiring Diagram WIRING DIAGRAMS ATTACHED...

Page 13: ...13 Commissioning Test Results COMMISSIONING TEST RESULTS ATTACHED...

Page 14: ...reset thermal overload protectors If the compressor fails it is strongly recommended that the air conditioner be returned to Kooltronic for service C Refrigerant Loss Kooltronic Air Conditioners are...

Page 15: ...ilter and secure in position by tightening the center screw 3 Lift filter up slightly to clear lower bracket and pull away from unit 4 Place new filter in lower bracket with flow arrows pointing towar...

Page 16: ...Relay Thermostat defective when applicable Failed Compressor Replace Compressor Ice on Evaporator Coil Insufficient Heat Load or Unit Contact Kooltronic Oversized for Application Failed Evaporator Bl...

Page 17: ...eceived by customer Number of parts to be returned Product description model and serial number Reason for return Action requested Contact name telephone FAX numbers and e mail address Pack unit in a s...

Reviews: