UAB KOMFOVENT we reserve the right to make changes without prior notice
V-C5.1_21-01
45
6.6. Control of air handling units through a web browser
You may not only monitor the operation of VERSO air handling units and the functionality of their
individual components, change settings and activate extra functions by means of control panel but also
by your computer. All you need is to connect the unit to the computer, local area network or the Internet
using a network cable.
Standard CAT 5
network cable
How to connect the unit directly to your computer:
1. Plug one end of the network cable into the controller port on the unit (see Picture 5.3 a) and the other end
to the computer.
2. Go to the properties of your network card and enter IP address, e. g. 192.168.0.200, and subnet mask
255.255.0.0.
3. Open the web browser on your computer and disable all proxy servers in the settings.
4. In the address bar of your web browser enter the IP address associated with the air handling unit; the
default IP address is 192.168.0.50. You can change it at any time on the control panel or from web browser
(see connection settings).
Note:
It is recommended to download the latest version of your web browser before use.
5. If the connection is successful, a window prompting to enter your user name and password appears:
Note:
the user name is
“user”
. The initial password is also
“user”
; after logging in, the user can later change the password
to any other of his/her choice (see user interface settings).
In case you forget your new password, you can restore the initial password
“user”
at any time through control panel settings.
6.7. Additional control options
6.7.1. Combined water coil control
For the air handling unit with the combined water coil (Combi-coil – heater and cooler in one) the
control of the mixing valve actuator is provided both under the air heating and cooling modes. The
actuator is connected to the control terminals of the heating circuit and operates only under the heat-
ing mode by default. However upon transfer of the feedback signal confirming that there is cold water
within the circulation system to the control terminals (IN4) of the external control (e.g., by connecting
additional device: thermostat, switch, etc.), the air cooling function will be activated, and the mixing
valve actuator (TG1) will be controlled under the air cooling mode.
Combi-coil control function must be ordered in advance.