UAB KOMFOVENT we reserve the right to make changes without prior notice
V-C5.1_21-01
24
EN
Roof mounting, if it was ordered separately
1
a
b
c
d
a+80
b+80
c
d+80
b+80
d+80
a+80
c
c
a
b
d
Joints need to be additionally sealed, if units are intended to be used outside. Seal-
ant is not included in unit set.
It is needed to protect water trap tubes from freezing in VERSO units. Please look
at the siphon installation guide.
On RHP units, air intake and outlet openings or hoods must be apart for at least 5
duct diameter distance.
If outdoor mounted ventilation unit will be stopped in cold temperatures, it is
needed to install additional air closing dampers in the supply and extract ducts
(room side). It must not allow the warm air from the premises circulate inside of
the unit when it is stopped, otherwise condensate may appear and could damage
electronic components.