2.4. Verso RHP units
Verso RHP information
Carefully, high pressure inside (up to 42 bar).
Inside the unit is refrigerant R410A, friendly to environment.
Before commissioning, make sure that the air handling unit is filled with refriger-
ant. This can be done by looking through the moisture indicator.
The unit washing, cleaning, maintenance is carried out as well as any other type of
device described in this manual.
In heating mode supply air temperature can range due to frozen evaporator.
Therefore, this unit is not recommended for use as a basic unit for heating, at low
outdoor air temperatures use with a secondary heater.
Verso RHP air handling (sizes 10–70) are supplied with two inspection sections (figure bellow). Ex-
haust air inspection section are supplied with drop eliminator, heating cable and pan for extract air coil.
Supply air inspection section are with pan and drop eliminator when design air flow velocity threw sup-
ply air coil are more than 2 m/s. If supply air velocity threw supply air coil are lower than 2 m/s where are
no pan and drop eliminator.
Verso RHP operation limits
For safe and efficient work units with integrated heat pump, has following limitations:
•
Air flow limitation as indicated in table and figure below. If one or both air flows are bellow switch
off limit (table 1) heat pump will be switched off and indication icon will occur in control panel (more
detail in page 32);
Table 1
Unit size
Air flow when heat pump switched off [m
3
/h]
Air flow when heat pump capacity are limited [m
3
/h]
10
900
1200
20
1800
2400
30
2700
3600
40
3600
4800
50
5000
7000
60
7000
9000
70
9000
12000
80
10000
14000
90
13000
16000