Variable air volume control mode calibration:
1. Before start of calibration the air distribution and exhaust devices in ventilation system should be
adjusted, all valves for variable air flow in a way enabling air supply to all ventilated premises should
be opened.
2. After switch on of the unit the VAV mode should be selected and calibration procedure should be
confirmed. After the end of the calibration, depending on the configuration of pressure sensors, VAV
mode status will change to Supply, Extract, Double.
3. After calibration the air handling unit further will operate in the previous mode.
• DCV
– direct controlled volume. The air handling unit will operate similarly as in the CAV mode, but
air volumes will be maintained directly in accordance with the values of the B6 and B7 analog input
signals of controller. After giving the signal 0... 10 V to the appropriate input, it will be converted
according to the current determined air volume. For example, if the maximum air flow of the unit is
1000 m
3
/h, setpoint in the panel – 800 m
3
/h, and the B6 input value – 7 V, the unit will supply con-
stant air volume of 560 m
3
/h, i. e., 70 % of the set value. The same applies to the exhaust air only by
B7 input (see picture 5.3 b).
Time / Date
Time and date is required for air handling unit operation planning.
Also it is possible to activate automatic daylight saving time.
Enable
Daylight saving time
Time/Date
Time
09:40
Day/Month
25/05
Year
2019
Daylight saving time
On
Connectivity
•
IP address and subnet mask. Setting is required when air handling unit is connected to PC network
or Internet.
•
Controller ID. Number that identifies the controller, when several air handling units are connected to
common network and controlled by one control panel.
6.5.4.2. Personalization
In this item for the user are presented menu language, measurement units
and other control panel settings.
Personalization
Language
English
Flow units
m
3
/h
Screen saver
On
Panel lock
Off
Touch sound
Click