4.2. Setting and Installing VERSO Air Handling Units
Before installing air handling unit it is important to remove transportation elements. If the unit was transported not
on the positioning frame, sections should be placed from wooden panels to positioning frame.
The unit is installed on even and solid base, location that was assigned to it. According to the unit weight,
which is indicated in technical specifications, dimensions and other important parameters special construction
calculations should be done.
If the unit is ordered with adjustable feet, unit can be leveled with its help. Leveling up to 50 mm.
If the surface on which the unit is installed is not even, the air handling unit
can distort, because of that doors may not close correctly, there may be
gaps between jointed sections.
It is advisable to put a gum seal between the air handling unit and the base.
It is forbidden to install the air handling units one on the other.
Wiring connection, – see electrical installation manual.
1
1
2
1. Fastening place for the key to the doors during air handling unit transportation
2. The key
Noise Caused by VERSO Air Handling Units
Air handling unit causes some acoustic noise (more specific data is available in the technical unit specification)
and this has to be taken into consideration when installing air handling unit. Comfort in the facilities depends not
only on the air handling unit, but also on the quality of the ventilation system, installment quality and other factors
(noise reduction means and etc).
Recommended:
•
To install air handling unit not closer than 500 mm from a wall (if needed – use additional noise reducing ma-
terials, for example, layers of mineral wool).
•
Make sure that vibration from the air ducts does not transmit to the building construction; therefore it is rec-
ommended to use flexible connectors, absorbing air duct holders. Air ducts must be selected so that air flow
would not create additional noise and vibration.
•
Air handling unit has to be installed on a fairly massive and solid base, considering mass of the unit and the
construction standards. It is recommended to lay gum sheets between air handling unit and the base.