5.1.1. Operation modes
In this menu item the user can select one of the five ventilation modes for the unit (see Chapter 2.1 “Ventilation Modes”).
Selecting the “Program” mode:
Mode selection
OPERATION MODES
Economy2
Comfort1
Comfort2
Special
Program
Economy1
You can select air volume (for supplied and extracted air separately) and desired temperature for each ventilation mode.
Air volume is set in the units specified in the user interface settings.
Supply flow
Extract flow
600
600
Setpoint
°C
Comfort1
m³/h
m³/h
21.0
“Special“ ventilation mode may also be used to block heating/cooling signals and disable humidification functions. To
disable a function, uncheck a box next to the setting.
Supply flow
Extract flow
1200
1200
Setpoint
°C
Special
m³/h
m³/h
21.0
Heating
Cooling
Humidifying