18
UAB KOMFOVENT we reserve the right to make changes without prior notice
RHP STANDARD_guide_21-03
EN
4.6. Functions
In menu item “Functions” you can activate or alter all functions of the unit. Press the function name or an arrow to display
the function settings.
Functions
Settings
Overview
Menu
Functions
1 / 2
Air quality control
Operation on demand
Outdoor compensated
ventilation
Summer night cooling
Minimum tempera-
ture control
Functions
2 / 2
Override function
Humidity control
1st additional zone
control
2nd additional zone
control
Scheduling
Function status is indicated in a box next to the function name:
Blank box: function is disabled.
Blue box: function is working.
Grey box: function is activated but not working.
In the settings of each function you can activate the function and alter operating conditions.
• Air quality control (AQC)
Selecting an air quality limit up to which the air handling unit will run during the activated
mode and above which the ventilation intensity will be automatically increased. Air quality limit
is set for two different ventilation modes during which the function will be used and the desired
value will change automatically as the mode changes. If the unit operates in a different ventilation
mode than the one set, air quality control function will be disabled automatically.
• Operation on demand (OOD)
Setting a critical air quality sensor value. The unit starts as soon as this value is exceeded.
• Outdoor compensated ventilation (OCV)
Setting winter and summer outdoor temperature limits for reducing ventilation intensity. When
the outdoor temperature is within the range of “Winter compensation start” and “Summer com-
pensation start”, the unit operates in a selected ventilation mode.
Reset settings
Enable
Setpoint 1
1000 ppm
Setpoint 2
880 ppm
Mode 1
COMFORT 1
Mode 2
COMFORT 2
Air quality control
Reset settings
Enable
Setpoint
1000 ppm
Operation on demand
Outdoor compensated...
Reset settings
Enable
Winter stop
-15 °C
Summer start
25 °C
Winter start
5 °C
Summer stop
35 °C