5.2.2. Outdoor compensated ventilation (OCV)
Setting winter and summer outdoor temperature limits for reducing ventilation intensity. When the outdoor tempera-
ture is within the range of “Winter compensation start” and “Summer compensation start”, the unit operates in a selected
ventilation mode.
Enable
Winter compensation stop
Winter compensation start
Summer compensation start
Summer compensation stop
OUTDOOR COMPENSATED VENTILATION (OCV)
-40.0
°C
°C
0.0
20.0
°C
°C
50.0
5.2.3. Minimum temperature control (MTC)
Setting a minimum desired supply air temperature.
Enable
Setpoint
MIN. TEMPERATURE CONTROL (MTC)
18.0
°C
5.2.4. Summer night cooling (SNC)
Setting two indoor temperatures for the function to start running and stop.
Enable
Stop when indoor
SUMMER NIGHT COOLING (SNC)
Start when indoor
25.0
°C
25.0
°C