Light Diode Indication:
1. No LED signal indication on the panel –
unit has been switched off.
2. LED shines steady green and text message is shown –
unit is switched on.
3. Automatic mode symbol is shown on the panel, while green LED shines –
unit is operating in automatic
mode according to weekly schedule.
4. LED blinks red and green and text message is shown – see 2.8 chapter.
5. LED shines steady red and text message is shown –
emergency unit shut down
(see 2.8 chapter).
6. Nothing is showing on the control panel –
unit does not have electric power supply.
Note:
By pressing any button on the panel automatically switching on the display backlight. Backlight is off after
30 seconds when no buttons are pressed.
2.4. Quick Ventilation Level Switchover
Three ventilation levels are projected in the unit. Each of them has its intensity (more detailed settings see
in the next chapter). There is possibility to switch ventilation level quickly from start-up window (2.3 Picture).
To increase ventilation intensity:
touch and hold
and at the same moment increase ventilation inten
-
sity by touching button.
To decrease ventilation intensity:
touch and hold
and at same moment decrease ventilation intensity
by touching button.
If ventilation intensity is changed using quick switchover and unit is op
-
erating according to weekly schedule, operation mode automatically is
changed to manual mode.
2.5. Unit Programmable Settings
By soft touching
button the parameters menu is entered. Menu window is selected by buttons ,
(see
further description). When menu window is selected, touch
for selecting desirable parameters and select
the value with , . To confirm the changes touch
button.
To return to previous menu or to start-up window touch button.
Note:
If touch sensitive buttons are inactive for 1 minute, start-up window is shown.
1. Unit operation modes setting
Two unit operation modes are possible: manual and automatic. In manual mode unit operates continuously
by set ventilation intensity. In automatic mode unit works according to weekly schedule (see further weekly
schedule setting).
Note:
If automatic operating mode is selected, there is a symbol
in the start-up window
.
2. Setting ventilation level
Ventilation equipment has three levels of ventilation. Fan intensity for every of the free levels can be attributed
separately for the supplied and exhausted air from 20 % to 100 %, in 1 % steps.
Intensity potentiometers on the automation box inside the air handling
unit are not used, their settings have no effect for the unit control when a
control panel with touch-sensitive buttons is connected.
3. Activation of the OVR function
Air handling units have the OVR function, which detailed description can be found in chapter 2.6. The OVR func
-
tion can be activated in two ways:
1. By the external control device.
Connection is described in chapter 1.4. After interconnecting (short-
circuiting) the FC contacts (see the electrical diagram), the unit will operate in the selected OVR mode and
after disconnection it will return to the previous operation mode.
2. By control panel.
In this case there is no need for additional connections to external control devices, the
function is activated from the panel, and the unit will operate in the chosen OVR mode until the internal timer
is active (from 1 to 90 minutes):