15
UAB AMALVA we reserve the right to make changes without prior notice
C4-16-01-v1
1. ELECTRICAL INSTALLATION MANUAL
Installation works can be performed only by the specialists that have required qualification. During installation
following requirements must be fulfilled.
It is recommended to lay control cables separately from power cables in
a distance no less than 20 cm.
Connector connection is performed strictly according to numeration giv
-
en in wiring diagram, or adequate markings (see wiring diagram).
When disconnecting unit sections, do not pull by connecting wires and
cables!
Before starting any operations inside the unit, make sure that the unit is
switched off and the power supply voltage is shut off.
1.1. Electric Power Supply Connection
Air handling unit voltage is 230 V AC; 50 Hz , therefore it is necessary to install the socket with grounding of
corresponding capacity (see wiring diagram). Electric power supply cable type is indicated in electric diagram.
Unit must be connected to the stationary installation by solid cable
through 10A circuit breaker with 30mA current leakage relay.
Before connecting unit to the electrical power supply, it is necessary to
check whether earthing has been installed properly in conformance with
electric safety requirements.
1.2. Control Panel Installation
1. Control panel must be installed in the room under given following conditions:
1.1. ambient temperature 0 °C ... 40 °C;
1.2. relative humidity limits 20 % ... 80 %;
1.3. protection must be ensured from accidentally vertically falling water drops (IP X2).
2. Installation height must be not less than 0,6 m from the ground.
3. Control panel connection is projected through the hole in its backside (see 1.2 Picture).
4. Control panel is fixed after screwing two holes on the fastening surface.
C4 PLUS Control Panel Connection
1.2 Picture
The length of cable connecting control panel and air handing unit can
not
exceed 150 m (see 1.2 Picture). Electr
ic power supply cable type is
indicated in wiring diagram..
When closing the panel window, do not bend the springs inside as this
may inhibit the functions of the panel buttons! (1.2 Picture) Disconnect
power supply prior to connecting the control panel!