background image

I.2

Prescribed use (Use as directed) of the servo amplifier

The servo amplifiers are components which are built into electrical equipment or machines, and can
only be used as integral components of such equipment.

The manufacturer of the machine must generate a hazard analysis for the machine, and take
appropriate measures to ensure that unforeseen movements cannot cause injury or damage to any
person or property.

The SERVOSTAR 600 family of servo amplifiers can be connected directly to symmetrically
earthed (grounded) three-phase industrial mains supply networks [TN-system, TT-system with
earthed (grounded) neutral point, not more than 5000 rms symmetrical amperes, 480VAC maxi-
mum].
The servo amplifiers must not be operated directly on power supply networks >230V without an
earth (ground) or with an asymmetrical earth (ground).
Connection to different mains supply networks (with additional isolating transformer)

ð

p.14.

Periodic overvoltages between outer conductor (L1, L2, L3) and housing of the servo amplifier may
not exceed 1000V (peak value).
Transient overvoltages (< 50µs) between the outer conductors may not exceed 1000V.
Transient overvoltages (< 50µs) between outer conductors and housing may not exceed 2000V.

If the servo amplifiers are used in residential areas, or in business or commercial premises, then
additional filter measures must be implemented by the user.

The SERVOSTAR 600 family of servo amplifiers is

only

intended to drive specific brushless

synchronous servomotors, with closed-loop control of torque, speed and/or position. The rated volt-
age of the motors must be at least as high as the DC-link voltage of the servo amplifier.

The servo amplifiers

may only

be operated in a closed switchgear cabinet, taking into account the

ambient conditions defined on page 17 and the dimensions shown on page 24. Ventilation or cool-
ing may be necessary to prevent enclosure ambient from exceeding 45°C (113°F).

Use only copper wire. Wire size may be determined from EN 60204 (or table 310-16 of the NEC
60°C or 75°C column for AWG size).

We only guarantee the conformance of the servo amplifiers with the standards for industrial areas
(page 7), if the components (motors, cables, amplifiers etc) are delivered by Seidel.

Option -AS-, restart lock for personnel safety

The -AS- restart lock is

exclusively

intended to provide safety for personnel, by preventing the

restart of a system. To achieve this personnel safety, the wiring of the safety circuits must meet the
safety requirements of EN60204, EN292 and EN 954-1.

The -AS- restart lock must

only

be activated,

when the motor is no longer rotating (setpoint = 0V, speed = 0rpm, enable = 0V).
Drives with a suspended load must have an additional safe mechanical blocking
(e.g. by a motor-holding brake).

when the monitoring contacts (KSO1/2 and BTB/RTO) for all servo amplifiers are
wired into the control signal loop (to recognize a cable break).

The -AS- restart lock may

only

be controlled by a CNC if the control of the internal safety relay is

arranged for redundant monitoring.

The -AS- restart lock must

not

be used if the drive is to be made inactive for the following reasons :

1.

-

cleaning, maintenance and repair operations

-

long inoperative periods

In such cases, the entire system should be disconnected from the supply by the personnel,
and secured (main switch).

2.

-

emergency-stop situations

In an emergency-stop situation, the main contactor is switched off
(by the emergency-stop button or the BTB-contact in the safety circuit).

10

SERVO

STAR

®

601...620 Installation Manual

General

06/02

Seidel

Summary of Contents for SERVOSTAR 601

Page 1: ...Assembly Installation Setup Edition 06 02 file 601620hw xxx EU order No 90162 NA M SS 004 0216 Digital servo amplifier SERVOSTAR 601 620...

Page 2: ...C AT is a registered trademark of International Business Machines Corp MS DOS is a registered trademark of Microsoft Corp WINDOWS is a registered trademark of Microsoft Corp HIPERFACE is a registered...

Page 3: ...ke 18 A 4 031 3 01 1 35 I 10 Regen circuit 19 I 11 Switch on and switch off behavior 20 I 11 1 Stop function to EN 60204 VDE 0113 20 A 4 031 3 6 I 11 2 Emergency Stop strategies 21 II Installation II...

Page 4: ...III 6 3 Interface for master slave operation encoder input 46 III 6 3 1 Connection to a SERVOSTAR master 5V signal level X5 46 A 4 031 1 16 3 2 III 6 3 2 Connection to encoders with 24V signal level X...

Page 5: ...68 V 2 6 Select motion task number Sample 68 V 2 7 Connection diagram 69 A 4 012 4 33 V 3 Expansion card PROFIBUS 70 V 3 1 Position of the connectors 70 V 3 2 Fitting the expansion card 70 A 031 4 62...

Page 6: ...lifier by touching any unpainted metal surface Avoid contact with highly insulating materials artificial fabrics plastic film etc Place the servo amplifier on a conductive surface l Do not open the un...

Page 7: ...ized testing laboratory in a defined configuration with the system components which are described in this documentation Any divergence from the configuration and installation described in this documen...

Page 8: ...Digital ground DIN German Institute for industrial Standards Disk Magnetic storage diskette hard disk EEPROM Electrically erasable programmable memory EMC Electromagnetic compatibility EMI Electromag...

Page 9: ...ch are currently available and the digital connection to automation systems can be found on the accompanying CD ROM in Acrobat Reader format system requirements WINDOWS 95 with Internet browser Acroba...

Page 10: ...ifiers may only be operated in a closed switchgear cabinet taking into account the ambient conditions defined on page 17 and the dimensions shown on page 24 Ventilation or cool ing may be necessary to...

Page 11: ...as a cut off length feedback cable pre assembled see application note Cables and connectors or both feedback connectors separately with feedback cable as length motor choke 3YL 20 p 79 for cable lengt...

Page 12: ...ptions l AS built in safety relay personnel safety starting lock out p 61 l I O expansion card p 66 l PROFIBUS DP expansion card p 70 l SERCOS expansion card p 72 l 2CAN Expansion module separated con...

Page 13: ...se width modulation 62 5 s l Freely programmable digital speed controller 65 s or 250 s l Integral position controller with adaptation possibilities for customer needs 250 s l Pulse direction interfac...

Page 14: ...ransformer is always required for 400 480V mains networks without earth ground and for networks with asymmetrical earth ground A 4 031 1 52 14 SERVOSTAR 601 620 Installation Manual General 06 02 Seide...

Page 15: ...I 6 Components of a servo system SERVOSTAR 601 620 Installation Manual 15 Seidel 06 02 General 24V supply fuses drive contactor terminals motor SERVOSTAR 600 PC Control PLC Option AS...

Page 16: ...ge max V 10 Input resistance to AGND kW 20 Digital inputs V low 0 7 high 12 36 mA 7 Aux power supply electrically isolated V 24 0 15 without brake A 1 Digital outputs open collector V max 30 mA 10 BTB...

Page 17: ...ength SERVOSTAR 601 610 1 1 5 mm 14 awg SERVOSTAR 614 620 2 5 mm 12 awg 600V 105 C 221 F shielded capacitance 150pF m Motor cables 25 to 100 m length with motor choke 3YL 20 consult our customer servi...

Page 18: ...below you can see the time and func tional relationships between the ENABLE signal speed setpoint speed and braking force During the internal ENABLE delay time of 100ms the speed setpoint of the serv...

Page 19: ...achieved by an automatic adjustment of the regen thresholds which vary because of tolerances The regen energy is distributed equally among all the amplifiers The combined power of all the amplifiers...

Page 20: ...elay so that personnel safety is ensured at the drive shaft p 61 The Stop functions are defined in EN 60204 VDE 0113 Para 9 2 2 9 2 5 3 There are three categories of Stop functions Category 0 Shut dow...

Page 21: ...ed by a changeover switch contactor e g Siemens 3RT1516 1BB40 and short circuited by resistors connected in a star configuration Category 1 If hazardous conditions can result from an emergency stop sw...

Page 22: ...This page has been intentionally left blank 22 SERVOSTAR 601 620 Installation Manual General 06 02 Seidel...

Page 23: ...motor power ca ble is used which includes cores for brake control the brake control cores must be separately shielded Earth ground the shielding at both ends p 28 l Install all heavy current cables w...

Page 24: ...r 4 hexagon socket screws to DIN 912 M5 Tool required 4 mm Allen key A 4 031 4 15 24 SERVOSTAR 601 620 Installation Manual Installation 06 02 Seidel SERVOSTAR 600 SERVOSTAR 601 610 SERVOSTAR 601 610 S...

Page 25: ...II 2 1 Dimensions A 4 031 4 14 SERVOSTAR 601 620 Installation Manual 25 Seidel 06 02 Installation SERVOSTAR 620 SERVOSTAR 601 603 606 610 SERVOSTAR 614...

Page 26: ...ol X which you will find in all the wiring diagrams indicates that you must take care to provide an electrically conductive connection with the largest possible surface area between the unit indicated...

Page 27: ...es separately Wire the BTB RTO contact in series into the safety loop of the installation Connect the digital control inputs to the servo amplifier Connect up AGND also if fieldbuses are used Connect...

Page 28: ...1 1 02 28 SERVOSTAR 601 620 Installation Manual Installation 06 02 Seidel p 50 p 51 p 36 p 36 p 37 p 36 p 37 p 39 p 38 p 40 p 41 p 42 p 43 p 44 p 45 p 46 p 48 SERVOSTAR 600 Reference Safety Instructio...

Page 29: ...ons for multi axis system A 4 031 1 19 SERVOSTAR 601 620 Installation Manual 29 Seidel 06 02 Installation SERVOSTAR 600 SERVOSTAR 600 SERVOSTAR 600 Power supply Reference Safety Instructions p 6 and U...

Page 30: ...II 3 3 Pin assignments A 4 031 4 21 30 SERVOSTAR 601 620 Installation Manual Installation 06 02 Seidel...

Page 31: ...outer covering of the cable and the shielding braid from the cores for the required length Secure the cores with a cable tie Remove the outer covering of the cable over a length of about 30mm without...

Page 32: ...ng All cables are suitable for use as trailing cables The technical data refer to the use as moveable cables Operating life 1 million bending cycles Cores mm Coretype Operation Temperature range C Ope...

Page 33: ...yourself on the amplifier but on a PC with the assistance of the setup software The PC is connected to the servo amplifier by a null modem cable The setup software provides the communication between...

Page 34: ...DOWS 3 xx DOS and OS2 In emergency operation is possible through an ASCII terminal emulation without user interface Interface settings 9600 bps no parity no handshake Unix Linux The software function...

Page 35: ...erfaces are shown in this Chapter The precise location of the connectors and terminals can be seen on page 30 The block diagram below is just an overview A 4 031 1 47 SERVOSTAR 601 620 Installation Ma...

Page 36: ...ternal 24VDC supply e g with insulating transformer Required current rating p 16 Integrated EMI filter for the 24V auxiliary supply III 1 3 DC link X7 Can be connected in parallel A patented circuit d...

Page 37: ...choke box 3YL 20 must be wired into the motor lead close to the amplifier III 3 External regen resistor X8 Remove the plug in link between the terminals X8 1 RB and X8 2 Rbint A 4 031 1 17 18 SERVOST...

Page 38: ...esolvers to the SERVOSTAR 600 If lead lengths of more than 100m are planned please contact our customer service The thermostat contact in the motor is connected via the resolver cable to the SERVOSTAR...

Page 39: ...drive tasks which require highly precise positioning or extremely smooth running If lead lengths of more than 50m are planned please consult our customer service The thermostat contact in the motor i...

Page 40: ...int Input SW SETP 2 terminals X3 6 7 Differential input voltage max 10 V resolution 12 bit scalable Standard setting torque setpoint Application examples for setpoint input SW SETP 2 adjustable extern...

Page 41: ...1 Tachometer voltage VTA speed The output delivers 10V at the preset limit speed Monitor 2 Current setpoint IDC torque The IDC monitor delivers 10V at the preset peak current Ipeak effective r m s val...

Page 42: ...put is freshly assigned to a pre programmed function then the data set must be stored in the EEPROM of the servo amplifier and the 24V auxiliary supply of the servo amplifier must be switched off and...

Page 43: ...e digital outputs DIGITAL OUT1 terminal X3 16 and DIGITAL OUT2 terminal X3 17 to output messages from pre programmed functions that are stored in the servo amplifier You can find a list of pre program...

Page 44: ...with the RESOLUTION parameter Encoder function ENCMODE Feedback system Resolution Zero position ROD 1 Resolver 16 1024 one per revolution only if A B 1 EnDat HIPERFACE 16 4096 and 8192 524288 2n one...

Page 45: ...lf a turn and for 6 pole resolvers it is within a third of a turn Exception If an encoder with a commutation track is used as the feedback unit then the upper 12 bits are set to 1 data invalid until a...

Page 46: ...or X3 must be joined together Signal diagram for encoders with RS422 or 24V output III 6 3 1 Connection to a SERVOSTAR master 5V signal level X5 This interface can be used to link several SERVOSTAR am...

Page 47: ...DGND connector X3 must be joined together III 6 3 3 Connection to a sine cosine encoder X1 This interface can be used to operate the SERVOSTAR as a slave mastered by a sine cosine encoder master slave...

Page 48: ...gear ing The number of steps can be adjusted so that the servo amplifier can be adjusted to the pulse direction signals of any stepper motor controller Various monitoring signals can be output The an...

Page 49: ...3 must be joined together III 7 2 Connection to stepper motor controller with 24V signal level X3 This interface can be used to connect the servo amplifier to a stepper motor controller with 24V sig n...

Page 50: ...h an optocoupler and is at the same potential as the CANopen interface The interface is selected and set up in the setup software Further notes can be found on page 33 With the optional expansion card...

Page 51: ...n AGND and DGND connector X3 must be joined together CAN bus cable To meet ISO 11898 you should use a bus cable with a characteristic impedance of 120 W The maximum usable cable length for reliable co...

Page 52: ...This page has been intentionally left blank 52 SERVOSTAR 601 620 Installation Manual Interfaces 06 02 Seidel...

Page 53: ...with dangerous levels up to 300 seconds af ter switching off the supply power Heat sinks and front panels of the amplifier can reach a temperature of up to 80 C 176 F in operation Check measure the he...

Page 54: ...um is 4 x motor standstill current I0 Limit speed maximum is the rated motor speed on nameplate Regen power maximum is the permitted regen resistor dissipation Station address unique address see setup...

Page 55: ...amplifiers or SR6Y6 for 6 amplifiers With the PC connected to just one servo amplifier you can now use the setup software to select all four six amplifiers through the preset station addresses and se...

Page 56: ...4V supply IV 2 2 1 Key operation The two keys can be used to perform the following functions Key symbol Functions U press once go up one menu item increase number by one press twice in rapid successio...

Page 57: ...ndard menu structure IV 2 2 4 Extended menu structure A 4 031 3 3 SERVOSTAR 601 620 Installation Manual 57 Seidel 06 02 Setup or p 55 p 55 p 55 the entry will be stored automatically when you exit the...

Page 58: ...erature internal temperature too high F14 output stage fault in the output stage F15 I t max I t max value exceeded F16 supply BTB RTO 2 or 3 phases missing in the supply feed F17 A D converter error...

Page 59: ...ference point no reference point set at start of motion task n10 PSTOP PSTOP limit switch activated n11 NSTOP NSTOP limit switch activated n12 motor default values loaded Only sine encoders with ENDAT...

Page 60: ...This page has been intentionally left blank 60 SERVOSTAR 601 620 Installation Manual Setup 06 02 Seidel...

Page 61: ...nctionality and the personnel safety when using the circuit recommendations in this documentation have been approved by the Trade Liability Association V 1 2 Functional description An additional conne...

Page 62: ...V 1 3 Block diagram V 1 4 Signal diagram sequence A 4 031 1 32 30 62 SERVOSTAR 601 620 Installation Manual Extensions Accessories 06 02 Seidel...

Page 63: ...d manner speed setpoint 0V 2 When speed 0 rpm disable the servo amplifier enable 0V 3 If there is a suspended load apply an additional mechanical block to the drive 4 Activate the AS option V 1 5 2 Fu...

Page 64: ...reas Even when several SERVOSTAR 600 are operating off a common mains supply and DC link it is possible to set up groups for separate working areas These groups can then be switched off sepa rately fo...

Page 65: ...V 1 6 2 2 Mains supply circuit A 4 031 3 05 SERVOSTAR 601 620 Installation Manual 65 Seidel 06 02 Extensions Accessories SERVOSTAR SERVOSTAR SERVOSTAR SERVOSTAR SERVOSTAR...

Page 66: ...l items such as screws fall into the open option slot l Push the expansion card carefully into the guide rails that are provided without twisting it l Press the expansion card firmly into the slot unt...

Page 67: ...V 2 4 Position of the connectors A 4 031 4 42 SERVOSTAR 601 620 Installation Manual 67 Seidel 06 02 Extensions Accessories Coding Plan view of the connectors as built in...

Page 68: ...nterrupted The motion task can also be continued by an appropriately configured digital input on the basic unit 2 In Start_MT I O Start of the motion task that has the number that is presented bit cod...

Page 69: ...V 2 7 Connection diagram A 4 012 4 33 SERVOSTAR 601 620 Installation Manual 69 Seidel 06 02 Extensions Accessories SERVOSTAR 600 I O 14 08...

Page 70: ...the servo amplifier V 3 1 Position of the connectors V 3 2 Fitting the expansion card If you want to retrofit the PROFIBUS expansion card into a SERVOSTAR 600 proceed as follows l Use a suitable scre...

Page 71: ...termination and transmission times are all described in the Installation guidelines for PROFIBUS DP Order No 2 111 from PNO the PROFIBUS User Organization V 3 4 Connection diagram A 4 031 1 41 SERVOS...

Page 72: ...n card The expansion card can be retrofitted from firmware version 4 30 Proceed as follows l Use a suitable screwdriver to lever off the cover of the option slot l Take care that no small items such a...

Page 73: ...BAUDRATE and the fibre optic connection If this LED flickers this indicates a low level of interference for Sercos communication or the optical transmitting power is not correctly adjusted to suit th...

Page 74: ...if the SERVOSTAR is at the end of the bus V 5 1 Position of the connectors V 5 2 Fitting the expansion module If you want to retrofit the 2CAN expansion module into a SERVOSTAR 600 proceed as follows...

Page 75: ...r the bus ter mination must be set to ON Otherwise the switch must be set to OFF condition as delivered V 5 4 Connector assignments RS232 CAN1 CAN2 X6A Pin Signal X6B X6C Pin Signal 1 Vcc 1 2 RxD 2 CA...

Page 76: ...voltage 24V 1 Max output current 5A Residual ripple 150mVss Switching peaks 240mVss Output fuse short circuit proof Temperature range 0 60 C 140 F Type of mounting DIN rails vertical mounting Keep a c...

Page 77: ...Input voltage 3 x 400VAC 10 Input current ca 1 1A Frequency 50 60Hz Primary fuse none Output voltage 24V 1 Max output current 20A Residual ripple 0 1 Output fuse short circuit proof Test voltage acc...

Page 78: ...resistor BARxxx Caution Surface temperature may exceed 200 C Observe the requested free space Do not mount to combustible surface A 4 947 4 22 78 SERVOSTAR 601 620 Installation Manual Extensions Acce...

Page 79: ...box 3YL 20 Technical data Nom data Sym DIM 3 YL 20 Rated current I0rms A Max 3 x 20 Frequency fmax kHz 8 3 Inductance L mH 1 2 A 4 030 4 10 SERVOSTAR 601 620 Installation Manual 79 Seidel 06 02 Exten...

Page 80: ...rself before touching the servo amplifier Avoid contact with highly insulating materials artificial fabrics plastic films etc Place the servo amplifier on a conductive surface max stacking height 8 ca...

Page 81: ...mostat has been activated feedback connector is loose or break in feedback cable wait until motor has cooled down then check why it became so hot tighten connector or use new feedback cable F07 messag...

Page 82: ...is too long increase Irms or Ipeak keep within motor data shorten setpoint ramp motor overheating Irms Ipeak set too high reduce Irms Ipeak drive too soft Kp speed controller too low Tn speed control...

Page 83: ...brake Brake in the motor which can only be used when the motor is at a standstill I I t threshold Monitoring of the actually required r m s current Input drift Temperature and age dependent alteratio...

Page 84: ...ange of direction Ring core Ferrite rings for interference suppression ROD Interface Incremental position output S Servo amplifier Control device for regulating the position of a servomotor Setpoint r...

Page 85: ...NA S62001 NA with AS option Option AS 90058 see order code in brackets Expansion card PROFIBUS DP 90056 OPT PB Expansion card SERCOS 90879 OPT SE Expansion card I 0 14 08 90057 OPT EI Expansion module...

Page 86: ...rface 36 mains supply networks 14 maintenance 80 master slave 46 monitor outputs 41 motor interface 37 motor choke connection example 29 motor holding brake 18 mounting position 17 multi axis systems...

Page 87: ...This page has been intentionally left blank SERVOSTAR 601 620 Installation Manual 87 Seidel 06 02 Appendix...

Page 88: ...erica Visit the North American Danaher Motion web site at www danahermotion com for Setup Software upgrades application notes technical publications and the most recent version of our product manuals...

Reviews: