TP-6461 1/08
93
Section 6, Component Replacement, Model KSS Switches
7. Remove the holding screws. Note the microswitch
labels on the insulators. See Figure 6-11.
8. Remove the microswitch assembly.
9. Remove
the
suspect
microswitch.
See
Figure 6-12.
10. Install the new microswitch into the assembly.
Note:
Replace SCN/SCE insulators in the correct
order. Normally, the SCE is closest to the
base.
11. Reinstall
the
microswitch
assembly.
See
Figure 6-13.
a. Install the holding screws.
b. Tighten the holding screws.
c. Connect the fast-on connections to the
microswitch terminals as noted in step 5.
Figure 6-11
Microswitch Insulator with Label
Figure 6-12
Microswitch
12. Clean the inside of the ATS.
13. Close and lock the enclosure.
14. Connect power to the ATS.
15. Enable the generator set startup.
a. Check that the generator set master switch is in
the OFF position.
b. Reconnect the generator set engine starting
batter(ies), negative (--) lead last.
c. Reconnect the battery charger, if equipped.
16. Move the generator set master switch to the AUTO
position.
17. Test the transfer switch operation by performing
the Automatic Operation Test Procedure described
in Section 4.5.4.
Note:
Do not leave the transfer switch in the Test
mode.
Figure 6-13
Microswitch Installation
Summary of Contents for KGP
Page 2: ......
Page 6: ...TP 6461 1 08 6 Notes ...
Page 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Page 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Page 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Page 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Page 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Page 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Page 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Page 125: ......